Isolated 4-20 mA Transmitter Output
CALIBRATION
RANGE
The transmitter output can be calibrated so that a 4 mA output is
produced for any number displayed on the meter. The 20 mA
output may correspond to any number displayed on the meter
(larger or smaller). However, best results are obtained with a
500-count difference between 4 and 20 mA displays.
The output will be linear (example: 4 mA = 0
°
, 20 mA = 1000
°
,
output is 6 mA at 125
°
.)
ACCURACY
±
0.1% F.S.,
±
.004 mA @ 25
°
C
NO EQUIPMENT
NEEDED
The 4-20 mA output from the Temperature Meter is calibrated
via the
ENTER
button without the use of a calibrator.
OUTPUT LOOP-
POWER
24 VDC ± 5% @ 20 mA, regulated. Maximum loop resistance is
1200
Ω
. Isolated from input signal.
ISOLATION
500 VDC or peak AC, input-to-output or input/output-to-power
line.
EXTERNAL
LOOP-POWER
SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply
Minimum loop
resistance
Maximum loop
resistance
24
VDC
10
Ω
600
Ω
35 VDC (external)
600
Ω
1000
Ω