Model PD650 Large Display Process Meter
Instruction Manual
39
Apply the signal for the first calibration point
Input 1 (
INPT 1
) flashes indicating that the meter
is ready to accept a signal for the first calibration
point. Apply the desired signal, typically 4 mA, and
press
ENTER
.
Inpt 1
Set the display for the first calibration point
The entire display will flash for three seconds. For
instructions see
Five Basic Digit/Display Setting
Instructions,
page 30.
-0.000
then
01.000
then
02.000
final
03.000
If an error message is displayed during calibration, refer to
Minimum Input Span
(Error Message)
, page 35.
Apply signal for the second calibration point
Input 2 (
INPT 2
) flashes indicating that the meter
is ready to accept a signal for the second
calibration point. Apply the desired signal, typically
20 mA, and press
ENTER
.
Inpt 2
Set the display for the second calibration point
Program the display as described above when the display
for the first calibration point was programmed.
-0.000
final display
12.000
Set the display for the remaining calibration points
If other calibration points were selected, they will be
displayed and can be set according to the procedure for the
first two points.
When the display for the last calibration point is accepted by
pressing
ENTER
, the meter will display total or process/rate.
Inpt 3