Model PD650 Large Display Process Meter
Instruction Manual
56
Figure 19. Programming Status of Set Point LEDs Assigned to Total
Note
To simplify programming, write down the desired programming
values prior to attempting to program the meter. The
Programmed
Parameter Settings
form located at the back of this manual provides
a convenient method to record the user settings; it also provides the
factory setting for most of the programmable parameters.
Press
ENTER,
then press
ENTER
again when the
set points (
SEtPtS
) function appears. The display
will scroll through the set points, press
ENTER
when the desired set point is displayed to program
that set point.
SEtPtS
To program set points values
Set point 1 (
SEt 1
) will be displayed. Press
ENTER
to
program set point 1 or wait and the display will move to the
next set point. When set point 4 (
set 4
) is shown, the meter
will exit the set points (
SetptS
) menu and move to the next
programming function.
The output function is displayed if the meter is equipped with
a 4-20 mA output option.
SEt 1
then
SEt 2
then
SEt 3
then
SEt 4
then
outPut
If
ENTER
is pressed while set point 1 (
SEt 1
) is
shown, the display will then show a flashing
number. Follow instructions below to program set
points assigned to process/rate and set points
(presets) assigned to total.
SEt 1
then
070.00
Set points assigned to process/rate
For set points that have been assigned to
process/rate during the
Setup
function, the
alarm # (1,2,3, or 4) and the
S
(set point) LED
will be illuminated. This indicates that the set
point for alarm # (1, 2, 3, or 4) is being
programmed.
Meter displaying alarm # 1 set
point