Helios Large Display Analog Input Batch Controller Instruction Manual
PD2-6210
52
Noise Filter (
filter
)
The noise filter is available for unusually noisy signals that cause an unstable process variable display.
The noise filter averages the input signal over a certain period. The filter level determines the length of
time over which the signal is averaged. The filter level can be set between 2 and 199. The higher the filter
level, the longer the averaging time and so the longer it takes the display to settle to its final value. Setting
the filter level to zero disables the filter function.
Noise Filter Bypass (
bypass
)
The noise filter bypass changes the behavior of the meter so that small variations in the signal are filtered
out but large abrupt changes in the input signal are displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.
Rounding Feature (
round
)
The rounding feature is used to give the user a
steadier display with fluctuating signals. Rounding
is used in addition to the filter function.
Rounding causes the display to round to the
nearest value according the rounding selected. See
examples below:
Modbus RTU Serial Communications (
serial
)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU
Serial Communication Protocol.
The meter may be connected to a PC for initial configuration via the onboard micro USB connection. For
ongoing digital communications with a computer or other data terminal equipment, an RS-232, or RS-485
option is required; see
Ordering Information
on page 5 for details.
Note: More detailed instructions are provided with each optional serial communications adapter.
Note: Refer to the Modbus Register Tables
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique
address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may
be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
Rounding
Selection
Actual
Value
Display
Value
Actual
Value
Display
Value
1
12.022
12.022
12.023
12.023
5
12.022
12.020
12.023
12.025
10
12.024
12.020
12.025
12.030
Warning!
Do not connect any equipment other than Precision Digital’s expansion
modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage
will occur to the equipment and the meter.
Do not disconnect the RJ45 connector located to the left of the power terminal
block. Doing so will disable the onboard digital I/O, RS-485 serial
communications, and M-Link functionality.
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30