Helios Large Display Analog Input Batch Controller Instruction Manual
PD2-6210
32
Setting up the Batch Controller (
setup
)
The
Setup
menu is used to select:
1. Input signal the controller will accept
2. Totalizer and batching features
3. Display units/tags
4. Decimal point position
5. Program menu for scaling or
calibration
6. Display parameter and intensity
7. Relay operation
8. 4-20 mA analog output scaling
Press the Enter button to access any menu
or press Up arrow button to scroll through
choices. Press the Menu button to exit at
any time.
Setting the Input Signal (
Input
)
Enter the
Input
menu to set up the meter to
display current (
mA
) or voltage (
volt
)
inputs.
The current input is capable of accepting
any signal from 0 to 20 mA. Select current
input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any
signal from -10 to +10 VDC. Select voltage
input to accept 0-5, 1-5, 0-10, or
10 VDC
signals.
Setting the Totalizer and Batching Features (
total
)
To simply not display the total, select alternative display parameters in the display (
dsplay
) menu.
Enable or disable the totalizer and batching features by selecting “
Yes
” or “
no
” after the input type has
been set up. If the totalizer features are disabled, all the totalizer and batching features and functions are
hidden from the menus. Level and process meter functions are added to the menus.
If disabling the
total
parameter by selecting
no
, please refer to the PD2-6000 manual
for instructions on setting up the meter parameters.
Notes: 1. The totalizer continues working in the background.
2. When selecting "no" for Total, the meter now functions as a PD2-6000 Process Meter. We
strongly suggest that you download and use the PD2-6000 instruction manual
while in this mode of operation.