PD8-6300 Pulse Input Rate/Totalizer, Counter & Tachometer
Instruction Manual
15
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Display Line 1: 0.60" (15 mm) high,
red LEDs
Display Line 2: 0.46" (12 mm) high,
red LEDs
6 digits each (-99999 to 999999),
with lead zero blanking
Display
Intensity
Eight user selectable intensity levels.
Default intensity is six.
Display
Update Rate
Rate: 10/sec to 1/100 sec (it is a function
of Low Gate setting)
Total: 10/second (fixed)
LED Status
Indicators
See
on page
details.
Overrange
Display flashes
999999
Display
Assignment
Display Line 1: Rate, total, grand total,
alternate (rate/total, rate/grand total,
rate/units, total/units, and grand total/units),
set points, max/min, Modbus input and
more.
Display Line 2: Same as Display Line 1;
plus units, tag or turned off.
Programming
Methods
Four SafeTouch through-glass buttons
when cover is installed. Mechanical buttons
can be used with the cover removed. Free
PC-based USB MeterView Pro
programming software.
Recalibration
All ranges are calibrated at the factory to
read frequency in Hz. No recalibration
required.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the meter is cycled.
Rounding
Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Password
Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
manually
Non-Volatile
Memory
Total and Grand Total values, and all
programmed settings are stored in
non-volatile memory for a minimum of ten
years if power is lost.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Fuse
Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
T6 Class operating temperature range
Ta = -40 to 60°C
T5 Class operating temperature range
Ta = -40 to 65°C
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
0 to 90% non-condensing
Max Power
Dissipation
Maximum power dissipation limited to 15.1 W
Connections
Power, signal, relays, mA out: Removable
screw terminal blocks accept 12 to 22
AWG wire
RS-485: Removable screw terminal block
accepts 16 to 30 AWG wire
Digital I/O: Removable screw terminal
blocks accept 16 to 30 AWG wire
Enclosure
Explosion-proof die-cast aluminum with
glass window, corrosion resistant epoxy
coating, color: blue
NEMA 4X, 7, & 9, IP68
Default conduit connections: Four ¾" NPT
threaded conduit openings and two ¾" NPT
metal conduit plugs with 12 mm hex key
fitting installed. Additional conduit opening
configurations may be available; verify
quantity and sizes on specific device
labeling during installation.
Mounting
Wall Mounting:
Four (4) mounting holes provided for
mounting meter to wall. See
Pipe Mounting:
Optional pipe mounting kit (PDA6848)
allows for pipe mounting. Sold separately.
See
for additional details.
Tightening
Torque
Screw terminal connectors:
5 lb-in (0.56 Nm)
Overall
Dimensions
6.42" x 7.97" x 8.47" (W x H x D)
(163 mm x 202 mm x 215 mm)
Weight
16.0 lbs (7.26 kg)
Warranty
3 years parts & labor. See Warranty
Information and Terms & Conditions on