PD8-6300 Pulse Input Rate/Totalizer, Counter & Tachometer
Instruction Manual
31
Setup and Programming
The meter may either be scaled (
SCALE
) without applying an input, calibrated (
Cal
)
by applying an input, or you may use the K-Factor menu to match the rate/totalizer
with a flowmeter’s k-factor (pulse/unit of measure).
The meter comes factory calibrated to NIST standards, so for initial setup, it is
recommended to use the K-Factor method or (
SCALE
) function.
Overview
There is one switch, located to the right of the input connector, which must be configured according to the input level
and type. The jumper J4 located inside the meter, behind the connector, is used to select the excitation voltage
(24 V*, 10 V or 5 V) which is supplied to the P+ and P- wiring terminals.
Setup and programming is done using MeterView Pro or through the programming buttons.
After power and input signal connections have been completed and verified, apply power to the meter.
*
Default setting
LED Status Indicators
LED
State
Indication
1-4
Steady
Alarm condition based on set and reset points, independent of relay
status in certain configurations. (Available on all meter
configurations, including those without relays installed)
1-4
Flashing
Relay interlock switch open
1-4 & M
Flashing
Relay in manual control mode
R
Steady
Rate
T
Steady
Total
G & T
Steady
Grand Total
▲
Steady
Total overflow. (“
oF
” is displayed to the left of total overflow and ▲
LED is illuminated)
M
Flashing
Analog output in manual control mode