PD8-6300 Pulse Input Rate/Totalizer, Counter & Tachometer
Instruction Manual
61
Troubleshooting Tips
Symptom
Check/Action
Serial Communications METER LINK
LED Indicator is off
Check:
1. Modular cable connection
2. Power to the device
If only the TX (or DATA IN) data status
LED is flashing when serial
communications attempted
Check:
1. Serial cable
2. Instrument address & baud rate
3.
Program address & baud rate
If both data status LEDs (TX and RX)
are off when trying to communicate
Remove all unnecessary cables and instruments from the bus.
Try getting the system to work with only one device (to ease
troubleshooting) and then expand the system one device at a time.
Communications slow
Increase the baud rate
Random communication errors
1. Increase the TX delay time
2. Decrease the baud rate
Other symptoms not described above
Call Technical Support for assistance
Note:
Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from factory
defaults and use the manual as a step by step programming guide, rather than a random approach to programming. To reset the
meter to factory defaults, see
Reset Meter to Factory Defaults
on page
In addition, for best results, we recommend using the
free MeterView Pro software for all programming needs.