PD8-6262 Explosion-Proof Dual Analog Input Flow Rate/Totalizer
Instruction Manual
18
Product Ratings and Approvals
FM
Enclosure: Type 4X; IP66
Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1, T5/T6
Class I, Zone 1, AEx d, IIC Gb T5/T6
Zone 21, AEx tb IIIC T90°C; Ta = -40°C to +65°C
T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C
Certificate Number: 3047283
CSA
Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
Class I Zone 1 Ex d IIC
Zone 21 Ex tb IIIC T90°C
-40°C < Tamb. < +60° C; Temperature Code T6
-40°C < Tamb. < +65° C; Temperature Code T5
Enclosure Type 4X & IP68
Certificate Number: 2531731
ATEX
II 2 G D
Ex d IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -40°C to +*°C
*T6 = -40°C to +60°C
*T5 = -40°C to +65°C
Certificate number: Sira 12ATEX1182
IECEx
Ex d IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -40°C to +*°C
*T6 = -40°C to +60°C
*T5 = -40°C to +65°C
Certificate Number: IECEx SIR 12.0073
Special Conditions for Safe Use:
Use suitably certified and dimensioned cable entry
device and/or plug. The equipment shall be installed
such that the supply cable is protected from
mechanical damage. The cable shall not be subjected
to tension or torque. If the cable is to be terminated
within an explosive atmosphere, then appropriate
protection of the free end of the cable shall be
provided. Cable must be suitable for 90°C.
Year of Construction
This information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
For European Community:
The ProtEX-MAX must
be installed in accordance with the ATEX directive
94/9/EC, and the product certificate Sira
12ATEX1182.