PD8-6262 Explosion-Proof Dual Analog Input Flow Rate/Totalizer
Instruction Manual
13
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Display Line 1: 0.60" (15 mm) high,
red LEDs
Display Line 2: 0.46" (12 mm) high,
red LEDs
6 digits each (-99999 to 999999),
with lead zero blanking
Display
Intensity
Eight user selectable intensity levels.
Default value is six.
Display
Update Rate
5/second (200 ms)
LED Status
Indicators
See
details.
Overrange
Display flashes
999999
Underrange
Display flashes
-99999
Display
Assignment
Display lines 1 & 2 may be assigned to show:
•
One or more rate channels: Channel A
(Ch-A), B (Ch-B), or C (Ch-C)
•
Toggle between rate channels: Ch-A &
Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and
Ch-A, Ch-B, & Ch-C
•
Total or grand total: Ch-A or Ch-B
•
Rate and total or grand total: Ch-A, Ch-B
•
Relay set points
•
Max/min values: Ch-A, Ch-B, or Ch-C
•
Toggle between any rate channel & units
•
Total and units: Ch-A or Ch-B
•
Toggle between totals: Ch-A & Ch-B;
Ch-A, Ch-B, and sum of Ch-A and Ch-B
•
Modbus input
Line 2 may also be set to show engineering
units or be off, with no display.
Programming
Methods
Four SafeTouch through-glass buttons when
cover is installed. Mechanical buttons can
be used with the cover removed. Free
PC-based USB MeterView Pro programming
software.
Noise Filter
Programmable from 2 to 199
(0 will disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of
calibrated span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the totalizer is turned off.
Rounding
Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Password
Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
manually
Non-Volatile
Memory
All programmed settings are stored in
non-volatile memory for a minimum of ten
years if power is lost.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Fuse
Required external fuse: UL Recognized, 5 A
max, slow blow; up to 6 totalizers may share
one 5 A fuse
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
T6 Class operating temperature range
Ta = -40 to 60°C
T5 Class operating temperature range
Ta = -40 to 65°C
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
0 to 90% non-condensing
Max Power
Dissipation
Maximum power dissipation limited to
15.1 W
Connections
Power, signal, relays, mA out: Removable
screw terminal blocks accept 12 to 22 AWG
wire.
RS-485: Removable screw terminal block
accepts 16 to 30 AWG wire.
Digital I/O: Removable screw terminal
blocks accept 16 to 30 AWG wire.
Enclosure
Explosion-proof die-cast aluminum with
glass window, corrosion resistant epoxy
coating, color: blue
NEMA 4X, 7, & 9, IP68
Default conduit connections: Four ¾" NPT
threaded conduit openings and two ¾" NPT
metal conduit plugs with 12 mm hex key
fitting installed. Additional conduit opening
configurations may be available; verify
quantity and sizes on specific device
labeling during installation.