background image

 

RSR-100 Remote Sensitivity Meter 

Operating Instructions

 

General Description 

The RSR-100 remote sensitivity meter is a tool to measure 

the sensitivity  of  SD-100  Series smoke detectors.  This 

battery-powered device is equipped with an infrared optical 

interface for reading data automatically sent by the smoke 

detector  every  5  seconds. The SD-100  decodes the 

sensitivity and status data, and displays the information on 

its LCD display. 

 

The RSR-100 may be used either as a hand-held device, or 

with a standard threaded extension pole. 

 

IMPORTANT:

 Use of the RSR-100 is designed to “...assure 

that  each smoke detector is within its listed and marked 

sensitivity  range...” per NFPA 72. The RSR-100  CANNOT, 

however, initiate a detector/sensor alarm. Sensitivity testing 

shall not be used as a substitute for alarm testing. 

 

RSR-100 Operation 

1. Turn the RSR-100 on by pressing and holding the button 

for  approximately 2 seconds until the meter  sounds  and 

the LCD displays the word “READY”. The “READY” status 

indicates that  the  RSR-100  is ready for accepting data 

from the SD-100 Series smoke detector. 

2. Place the remote sensitivity meter over the IR LED on the 

smoke detector being tested, which is close to the words 

“DO NOT PAINT”.  (See Figure 1), Position the meter 

either vertically or at an angle (see Figure 2). 

 

 

 

 

3. Hold the remote sensitivity meter in this position up to 10 

seconds until the meter sounds and the meter’s red LED 

illuminate. 

4. The LED and sounder indicate a valid reading is received. 

The  Meter reading  and stats for the detector will be 

automatically displayed on the reader (See Table 1). The 

Meter will continue to display this information for up to 8 

minutes or until the meter is reset.   

 

 

 

 

NOTE: 

No further readings may be taken until the reader 

is reset. 

 

5. To measure the sensitivity of the next detector, reset the 

meter  by momentarily pressing the button. The LCD will 

again display the word “READY”. Repeat step 2, 3 and 4, 

as necessary. 

6. When finished, turn off the reader by pressing and holding 

the  button for approximately 2 seconds until the reader 

sounds and LCD turns off. 

Figure 1: Meter location on 

SD-100 Series Detector

 