background image

Table 1: RSR-100 Status Indications 

Indication 

Action 

GOOD 

The detector is within its sensitivity 

range. No  action is necessary at this 

time. 

SERVICE 

The smoke detector’s sensing chamber 

requires cleaning for continued reliable 

operation. Refer to the SD-100 Series 

installation and maintenance instructions 

for proper maintenance procedures. 

REPLACE  The smoke detector failing and should be 

replaced immediately. 

 

NOTE: 

When the batteries in the RSR-100 get low, the LCD 

display  will read “LOW BATT”. Once the low battery 

condition is  reached, the reader will no longer function. 

Replace batteries to restore operation of the RSR-100. 

 

 

The RSR-100 automatically turns off when not used after 8 

minutes. To conserve the battery life of the Remote 

Sensitivity Meter, it is recommended that the reader be 

turned off when not in use. To turn off the meter, press and 

hold the button for approximately 2 seconds until the reader 

sounds. 

 

 

Specifications 

Power supply: two AA alkaline batteries 

Operating Temperature: 0 to 37.8°C 

Storage Temperature (without batteries): -15 to 60°C 

Operating Humidity: 10 to 90% RH non-condensing or icing 

 

 

 

WARNING 

The Limitations of the RSR-100

 

The RSR-100 is designed to “... assure that each smoke detector is within its listed and marked sensitivity range ...” as 

per NFPA 72. The RSR-100 CANNOT, however, initiate a detector/sensor alarm. Therefore, the meter meets only part 

of NFPA 72 testing standards.   

 

Slight fluctuations in readings may be experienced on any device at any given time and do not indicate a defect or 

sensitivity shift, provided the reading is within the specified range. These fluctuations are to be expected. The RSR-100 

and its associated smoke detectors/sensors contain electronic parts and, though they are designed to last over 10 years, 

any of these components can fail at any time. Therefore, it is recommended to test your smoke detectors/sensors as per 

NFPA 72 at least semiannually. Regular cleaning and testing of your fire detection system will measurably reduce your 

product liability risks and minimize nuisance alarms.

 

 

 

 

 

MIRCOM GROUP OF COMPANIES 

NO.  LT-1146 

Revision  1 

Title 

RSR-100 Remote Sensitivity Meter 

Operating Instructions 

Confirmed 

Author 

Date 

(YY-MM-DD) 

 

 

2012-09-06 

Отзывы: