page no. 33 of 36
Vision Maxi
User Instructions Doc Ref M609 issue 1.0 June 2021.
Reference conditions
Environment T
External T
(1)
Cooling mode tests (EN 14511)
DB 27°C - WB 19°C
DB 35°C - WB 24°C
(2)
Heating mode tests (EN 14511)
DB 20°C - WB 15°C
DB 7°C - WB 6°C
(3)
Heating mode tests
DB 20°C - WB 15°C
DB -7°C - WB -8°C
(4)
Internal side sound pressure measured in semi-anechoic chamber at a distance of 2 m.
(5)
Internal side sound pressure measured in accordance with regulation EN 12012
Operating limits
Indoor environment T
External environment T
Maximum operating temperature in cooling mode
DB 35°C - WB 24° C
DB 43°C - WB 32° C
Minimum operating temperature in cooling mode
DB 18°C
DB -5°C
Maximum operating temperatures in heating mode
DB 27°C
DB 24°C - WB 18° C
Minimum operating temperatures in heating mode
DB 5°C
DB 10°C
5.2 Dimensions
..2.0
Models
m.u.
15 HP
Product dimensions and weight
Total widh
mm
1010
Total height
mm
549
Total depth
mm
165
Empty weight
kg
41.0
Wall hole diameter
mm
202
Wall holes distance
mm
293
5.3 RED Compliance Statement
Compliance with 2014/53/EU Radio Equipment Directive
(RED).
In accordance with Article 10.8(a) and 10.8(b) of the RED, the
following table provides information on the frequency bands
used and the maximum RF transmit power of the product for
sale in the EU:
Frequency range (MHz)
Max. Transmit Power
2400-2472
<20
Hereby, the company declares that the device is in
compliance with Directive 2014/53/EU.
For declarations of conformity, certificates and other
certification details please consult the website.
This equipment should be installed and operated with a
minimum distance of 20 centimetres between the radiator
and your body.
Safety
This equipment is designed with the utmost care for the
safety of those who install and use it.
However, special attention must be paid to the dangers
of electric shock and static electricity when working with
electrical equipment.
All guidelines must therefore be allowed at all times to ensure
safe use of the equipment.