background image

page no. 24 of 36 

    

Vision Maxi

 User Instructions  Doc Ref M609 issue 1.0 June 2021.

  

block (recommended connection for installation of the 
equipment at the top of the wall).

GR

 

 Grey

BR

 

 Brown 

YG

 

 Yellow-Green

BL

 

 Blue

CP

 

 Presence contact

N

 

  Neutral

L

 

  Phase

IG

 

 System main switch

GR

GR

C P

L

N

I G

GR

BL

YG

BR

This operation must be only be carried out by the 

installation or Technical Assistance Centre.

To carry out direct connections and substitute the power 
cord using the cable in the wall, proceed as follows: 
–  access the terminal block

–  Disconnect the power cord from the terminal block.

–  Connect the wall cable, checking that the power supply 

line has a suitable earth connection 

–  The power supply line has a suitable earth connection 

and that it is sized for the maximum absorption of the 

conditioner (minimum cable section equal to 1.5 mm² and 
2.5 mm² for ELEC version).

 CP occupancy contact input connection

When the CP contact opens (very low voltage, connected to 
a free non-live contact) the appliance is put is stand-by and 
CP appears on the display.
Through this contact it is possible to connect an external 
device that inhibits operation of the unit such as: window 
opening contact, remote on/off, infrared presence sensor, 
activation badge etc. 

We recommend using a double insulation cable.

For the ELEC versions with resistor, disconnecting voltage 
from the device abruptly is prohibited in order to prevent 
internal overheating! Use the CP contact that places the 
device in standby and guarantees correct post-ventilation.

GR

 

 Grey

BR

 

 Brown 

YG

 

 Yellow-Green

BL

 

 Blue

CP

 

 Presence contact

GR

GR

C P

GR

BL

YG

BR

 Configuration with the nebulizer 3.0 

When installing the nebulizer 3.0 it's very important to follow 
the  indicated procedure to avoid a systematic alarm and the 
possible failure of the nebulizer.
This procedure, enabled through the display of the air 
conditioner, modifies the default settings of the drain pan of 
the appliance by disabling its automatic closure during the 
summer season.

This procedure is used to avoid that during the summer 
season, with the opening of the drain valve of the drain 
pan, the condensate itself is poured all in the 3.0 nebulizer 
installed under the appliance.
The condensate drain will always remain open in both 
seasons, guaranteeing a regular flow of condensation.

– 

To activate this function: 

Press the cooling mode key  

 on the display of the appliance 

The symbol “En” will appear

– 

press for 15 seconds the key 

 

The symbol “ds” will appear. Let the display go back to the main screen

2.13   High/low installation configuration

The unit can be installed either at the bottom of the wall 
(adjacent to the floor) or at the top of the wall (adjacent to 
the ceiling).
The unit is supplied for low wall installation with the air outlet 
from the bottom to the top.
For high-wall installation:

–  purchase the the lower cover decorative kit code GB0737II. 

High wall installation is recommended if the unit is to be 
used for cooling only.

If the unit operates in cooling and heating or heating only, 
low wall installation is recommended.

Содержание Vision Maxi

Страница 1: ...w w w p o w r m a t i c c o u k Doc Ref M609 Issue 1 0 June 2021 Vision Maxi Installation Servicing Manual Issue 1 0 June 2021...

Страница 2: ...our behalf Conditions of Guarantee 1 The air conditioner must have been installed by a competent installer and in accordance with the manufacturer s instructions and any building regulations and local...

Страница 3: ...tive and implementing regulation 206 2012 EU and Italian implementing regulation Legislative Decree no 15 of 16 02 2011 F Gas Regulation 2014 517 EU on fluorinated greenhouse gases And subsequent amen...

Страница 4: ...4 2 6 Unpacking p 14 2 7 Handling without packaging p 15 2 8 Installation site p 15 2 9 Installation minimum distances p 16 2 10 Positioning p 16 2 11 Condensation drain preparation p 20 2 12 Electric...

Страница 5: ...age no 5 of 36 Vision Maxi User Instructions Doc Ref M609 issue 1 0 June 2021 5 Technical information p 32 5 1 Technical data p 32 5 2 Dimensions p 33 5 3 RED Compliance Statement p 33 5 4 Safety p 33...

Страница 6: ...ammable and odourless Avoid proximity to sources of ignition in continuous operation open flames gas appliances electric stoves lighted cigarettes etc Instructions Read the instructions carefully befo...

Страница 7: ...re is pressurised refrigerant gas and live electrical components inside the appliances The installation and subsequent maintenance phases must be carried out exclusively by authorised and qualified pe...

Страница 8: ...to off It is forbidden to modify the safety or adjustment devices or adjust without authorization and indications of the manufacturer It is forbidden to pull unplug or twist the device s electric cabl...

Страница 9: ...efore invalidates the warranty 1 8 Destination of use These appliances have been designed for conditioning and or heating rooms and they must be destined solely for this purpose in accordance with the...

Страница 10: ...i lifting bracket 11 External air expulsion 12 Remote control 13 Internal exchanger 14 External fan 15 Condensation pump 16 Condensation drain valve 17 Floater 18 External exchanger 19 External air pr...

Страница 11: ...L00771II Recessed formwork for corner installation with left hand exit Compatible with only DC Inverter versions All L00772II Accessories supplied separately Grilles and accessories Kit n 2 external...

Страница 12: ...ut to ensure that the risk of combustion is minimised before starting work on systems containing flammable refrigerants The appliance must be protected against accidental impacts to prevent mechanical...

Страница 13: ...when the load is lifted off the ground Avoid dangerous situations when using a hoist to lift the appliance During transportation the appliance must be kept in vertical position Avoid exposure to sour...

Страница 14: ...e The equipment must always be handled vertically Check if there is refrigerant inside the package using an electronic leak detector suitable for the system refrigerant If it is present the refrigerat...

Страница 15: ...ecessary to check carefully that the weight of the unit does not exceed the regulations in relation to the number of people used 2 8 Installation site The location of the appliance must be determined...

Страница 16: ...use damage to persons or property if it should detach from its base The unit should not be installed in a position where the air flow is aimed directly at the people nearby Provide the following a nea...

Страница 17: ...or models 15 HP DC Inverter B C F IN OUT D E A Hold the template in the correct position with tape Preliminary warnings The wall mounting bracket supplied as an accessory is required to position the u...

Страница 18: ...xternal side The maximum length of the holes is 1 meter Curves are prohibited To prevent the creation of large quantities of dust and debris in the room it is recommended to couple the core drill to a...

Страница 19: ...r so that the flaps are in vertical position insert the counterflange in the hole toward the interior of the room rotate it so that the hooks are in vertical position pull the chains so that the sprin...

Страница 20: ...If the line flows into a container e g a tank do not close the container hermetically and avoid immersing the draining pipe into the water The hole for the condensation pipe must always slope towards...

Страница 21: ...eakage of water The drainage pipe must be insulated for sections running inside houses in order to prevent condensate formation on its surface If needed it is possible to empty the condensation collec...

Страница 22: ...e of minimum 3 mm or using a device enabling the complete disconnection of the appliance in overvoltage III category conditions Please check that the power supply is provided with suitable protections...

Страница 23: ...apter Removal of aesthetic panels and grilles p 27 To access the connections unscrew the screws of the electrical panel remove the electrical panel cover Connection The appliance leaves the factory fu...

Страница 24: ...the CP contact that places the device in standby and guarantees correct post ventilation GR Grey BR Brown YG Yellow Green BL Blue CP Presence contact G R G R C P G R BL YG BR Configuration with the ne...

Страница 25: ...esthetic lower cover kit Code GB0737II 2 Fixing screws supplied with the optional kit GB0737II 3 Right support bracket for the flap A B 1 3 2 180 Configuration After adjusting the air outlet flap posi...

Страница 26: ...y for 3 seconds The lock remains active also for the next operations performed via remote control and in the event of a power failure 2 17 hotel function Keep the key pressed for 10 seconds If the En...

Страница 27: ...9 issue 1 0 June 2021 2 19 Removal of aesthetic panels and grilles 2 1 2 20 Assembly of aesthetic panels and grilles To assemble positioning the aesthetic panel insert the two screws Screw in the two...

Страница 28: ...nces electric stoves lighted cigarettes etc Smoking in the vicinity of the appliance is prohibited Using a mobile phone near the appliance is prohibited Using leak detectors with halogen lamps is proh...

Страница 29: ...c panels and grilles p 27 For grid assembly operations see chapter Assembly of aesthetic panels and grilles p 27 extract the filter by lifting it remove the dust from the filter with a vacuum cleaner...

Страница 30: ...m irons hot plates etc Displayed faults In the event of a malfunction the display shows an alarm code The appliance still retains some functions see the OPERATION column Alarm Cause Function E1 Faulty...

Страница 31: ...rvice During heating condensation should drain freely through the specific pipe In the event of an alarm check that the condensation pipe is not bent or obstructed thus preventing the water from flowi...

Страница 32: ...minimum fan speed m h 300 Aeraulic data outdoor Ventilation speed Nr 3 Air flow at the maximum fan speed m h 550 Air flow at the medium fan speed m h 460 Air flow at the minimum fan speed m h 400 Ele...

Страница 33: ...ight mm 549 Total depth mm 165 Empty weight kg 41 0 Wall hole diameter mm 202 Wall holes distance mm 293 5 3 RED Compliance Statement Compliancewith2014 53 EURadioEquipmentDirective RED In accordance...

Страница 34: ...page no 34 of 36 Vision Maxi User Instructions Doc Ref M609 issue 1 0 June 2021 Notes...

Страница 35: ...page no 35 of 36 Vision Maxi User Instructions Doc Ref M609 issue 1 0 June 2021 Notes...

Страница 36: ...e mail info powrmatic ie web www powrmatic ie Getting In Touch Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to c...