49
Step 3: After pressing the “Battery Start” button, UPS will enter into Standby mode. Refer to the diagram
below for LCD display.
Step 4: Before UPS enters into shutdown mode, please press “POWER” button for 2 seconds immediately as
shown in the diagram below.
Step 5: Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6: Switch ON the output breaker (Q3). Cold start startup procedure is complete.