7
Interface and Communication
This UPS comes equipped with various communication devices. Please refer to chapter 4 Interface and
Communication for further details.
Power Stage/Module
Each power stage/module includes a power factor correction rectifier, a battery charger, an inverter and
control circuit.
No.
Item
Description
Fan
Air enters the power stage/module through the front grills and exhausted
through rear of the module. Please do not block the ventilation vent port.
DIP Switches
There are three DIP switches for power stage/module address setting. In the
same cabinet, each power stage/module ID MUST be exclusive. Please refer to
Table 2-1 Power Stage/Module ID
Battery Start Button When AC input is not existing, use this button to start battery power for UPS.
FAULT LED
ON
The power stage/module is in fault condition.
ON/OFF 0.5 sec
The power stage/module IDs in conflict.
RUN LED
ON
The power stage/module normally works as a slave
unit.
ON/OFF 0.5 sec
The power stage/module normally works as a master
unit.
ON/OFF 0.15 sec
The CAN BUS communication doesn’t work.
1.
Dry contact port X1
2.
Dry contact port X2
3.
SNMP slot (SNMP card
optional
)
4.
Extended communication
slot(Extra Comm. card
optional
)
5.
RS-232 port
6.
USB port