41
5-2. Operation Mode
This UPS is a three-phase, four-wire on-line, double-conversion and reverse-transfer UPS that permits
operation in the following modes:
Standby Mode
Line Mode
Battery Mode
Bypass Mode
ECO Mode
Shutdown Mode
Maintenance Bypass Mode (manual bypass)
5-2-1. Standby Mode
Upon connecting to utility input power, the UPS is in Standby mode unless UPS is turned on (if BYPASS
enable setting is Disabled), and charger function will be active when the battery is connected. The load is
not powered under this mode.
Standby Mode Diagram
5-2-2. Line Mode
In Line Mode, the rectifier delivers power from the mains and supplies DC power to the inverter and the
charger charges the battery. The inverter filters the DC power and converts it into pure and stable AC power
Содержание VFI 100K CPG 3/3 BX