48
Step 5: Make sure that there is no warning or fault event. If yes, please refer to Chapter 7 Troubleshooting
to resolve it.
Step 6: Press POWER button for two seconds to enter into Line Mode as shown below.
After POST (Power-On Self-Test), the UPS will enter into the Line mode.
Step 7: Switch ON the output breaker (Q3). AC startup procedure is now complete.
6-2. Cold Start Startup
Step 1: Switch ON the battery Breaker.
Step 2: Press the “Battery Start” button on any one of power stages/modules to start up the control power.