2
Do not tilt the cabinets more than 10 degree.
The disconnection device should be installed on the input current break line and neutral
conductors - four poles for three phases.
1-4. Connection Warnings
•
This UPS should be connected with TN grounding/earthing system.
•
The power supply for this unit must be three-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded.
•
Use of this equipment in medical instrument of any life-sustaining equipment where failure of this
equipment can reasonably be expected to cause the failure of the life-sustaining equipment or to
significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable mixture with air, oxygen or nitrous oxide.
•
Connect grounding terminal of power stage to a grounding electrode conductor.
•
In accordance with safety standard EN-IEC 62040-1, installation has to be provided with a
《
Backfeed
Protection
》
system, for example a contactor, which will prevent the appearance of voltage or dangerous
energy in the input mains during a mains fault (see figure 24 and conforms to the wiring diagram of
«Backfeed Protection» depending on the phase input).
There can be no derivation in the line that goes from the «Backfeed Protection» to the UPS, as
the standard safety would be compromised.
•
Warning labels should be placed on all primary power switches installed in places away from the unit to
alert maintenance personnel of the presence of a UPS in the circuit. The label will bear the following or
an equivalent text:
•
The isolation device must be rated to carry the UPS input current.
Before working on this circuit
-
Isolate Uninterruptible Power Supply (UPS)
-
Then check for Hazardous Voltage between all terminals including the protected
earth
Risk of Voltage Backfeed
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY