background image

 

V1.01 

 

 

42 

 

Error reference code 

 

  

01 

Fan  is locked when inverter is off 

 

  

02 

Inverter transformer over temperature 

 

   

03 

Battery voltage is too high 

 

   

04 

Battery voltage is too low 

 

   

05  

Output short circuited  

 

   

06 

Inverter output voltage is high 

 

   

07 

Overload time out 

 

   

08  

Inverter bus voltage is too high  

 

   

09 

Bus soft start failed 

 

   

11 

Main relay failed 

 

   

21 

Inverter output voltage sensor error 

 

   

22 

Inverter grid voltage sensor error 

 

  

23 

Inverter output current sensor error 

 

   

24 

Inverter grid current sensor error 

 

   

25 

Inverter  load current sensor error 

 

   

26 

Inverter grid over current error 

 

   

27 

Inverter radiator over temperature 

 

Содержание LfeLi-48100TB

Страница 1: ...V1 01 1 USER MANUAL V1 01 PB UPS 2 2 24 Li PB UPS 3 5 24 Li PB UPS 5 5 48 Li PB UPS 10 10 48 Li PB UPS 15 15 48 Li...

Страница 2: ...THE PROGRAMMING THAT CAN ACTIVATE THIS THE PB UPS SYSTEMS ARE PROVIDED AS A WHOLE CONSISTING OF INVERTER BATTERIES BATTERY BOX CABLES AND ACCESSORIES FUSES IT IS IMPORTANT THAT THE SYSTEM IS INSTALLE...

Страница 3: ...g the device 16 Battery connection 17 Recommended battery cable and terminal size 18 AC input output terminal 18 PV connection 20 PV module selection 21 final assembly 23 Communication Connection 23 E...

Страница 4: ...charge voltage 34 Program 19 battery minimum voltage settings 35 Program 20 switch from battery to utility discharge 35 Program 21 switch from battery to utility charge 35 Program 22 Automatic Page Tu...

Страница 5: ...el in mono phase setup 54 Three phase setup 56 Connecting solar panel 57 Error reference code 57 Settings 58 Parallel in mono phase PB UPS 10 10 48 PB UPS 15 15 48 58 Three phase configuration PB UPS...

Страница 6: ...g characteristic 74 charging voltage 75 Temperature compensation 75 STORAGE 76 Environment 76 Self discharge 76 OCV versus SOC 76 Recharging 77 LIFESPAN 78 Lifespan at Floating 78 Lifespan at Deep Cyc...

Страница 7: ...antling 88 USING FeLiPo4 BATTERIES 88 Charging 88 Discharging 89 USE OF THE BLUETOOTH APP 89 GRAPHS 92 FAQ 95 POSSIBLE ERRORS AND THEIR CORRECTION 96 WARRANTY HANDLING 97 SERVICE 98 SPECIFICATIONS PB...

Страница 8: ...115 INSTALLATION GUIDE 116 Installation Precautions 116 Preparation of the installation 119 Installation and cabling 121 Standard installation of the cabinet 121 Electrical maintenance 122 Battery mai...

Страница 9: ...5 5 48 147 PB UPS 10 10 48 151 PB UPS 15 15 48 156 PB UPS 2 2 24 Li 161 PB UPS 3 5 24 Li 165 PB UPS 5 5 48 Li 169 PB UPS 10 10 48 Li 173 PB UPS 15 15 48 Li 177 MOUNTING FUSEHOLDERS AND BUSBAR 181 BUSB...

Страница 10: ...V1 01 10...

Страница 11: ...V1 01 11 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48...

Страница 12: ...V1 01 12...

Страница 13: ...al power supply conditions or operate environmental damage SAFETY INSTRUCTIONS WARNING This chapter contains important safety and operating instructions Read and keep this manual for future reference...

Страница 14: ...ls Please refer toINSTALLATION section of this manual for the details 10 Fuses 1 piece of 200A 58VDC for 3KW 4KW and 5KW are provided as over current protection for the batterysupply 11 GROUNDING INST...

Страница 15: ...not in use 5 Function buttons 13 Parallel communication port 6 Power on off switch 14 Parallel dipswitches 7 AC input utility 15 Potential free contact 8 AC output loads 16 USB INSTALLATION Unpacking...

Страница 16: ...is inverter at eye level in order to allow the LCD display to be read at all times For proper air circulation to dissipate heat allow a clearance of approx 200 mm to the side and approx 300 mm above a...

Страница 17: ...st be done by qualified personnel warning It is very important for system safety and efficient operation to use suitable cable for battery connection To reduce the risk of injury use the the correct r...

Страница 18: ...ls until the terminals are properly connected PAY ATTENTION Before making final DC connection or closing DC breaker disconnector must be connected to positive and negative must be connected to negativ...

Страница 19: ...ow to implement ac input output connection 1 Before making ac input output connection please open the DC protector or decoupler first 2 Remove insulation sleeve 10mm for six conductors And shorten pha...

Страница 20: ...ind of damage check with the manufacturer of the air conditioner if it is equipped with an installation delay function Otherwise this inverter charger will cause overload error and turn off the output...

Страница 21: ...everal PV modules in series connection See the table below Note Vmp panel max power point voltage PV charging efficiency is maximized when the PV system voltage is close to the Best Vmp Maximum PV mod...

Страница 22: ...tive and negative conductors 2 Check the correct polarity of the connection cable of PV modules and PV input connectors Then connect the positive pole of the connection cable to the positive pole of t...

Страница 23: ...t inverter and PC Insert a supplied CD into a computer and follow the on screen instructions to install the installing surveillance software Consult the software user manual in the CD for the detailed...

Страница 24: ...switch located on the button on the case to turn on the device Control and display panel The control and display panel shown in the graph below is located on the front panel of the drive It includes t...

Страница 25: ...ter Flashing Warning condition occurs in the inverter Function Keys Function Keys Description menu Enter reset mode or setting mode go to previous selection up Increase the setting data down Decrease...

Страница 26: ...battery charging status STATUS Constant Currentmode Constant Voltage mode Battery voltage LCD display 2V cel 4 bars will flash in turns 2V cel 2 083V cel Bottom bar will be on and the other threebars...

Страница 27: ...l 1 817V cel 1 9V cell 1 9V cel 1 983V cell 1 983V cell load 20 1 867V cell 1 867V cell 1 95V cell 1 95V cell 2 033V cell 2 033V cell Load Information Indicates overload Indicates the load level by 0...

Страница 28: ...ration Indicates unit alarm is disabled LCD Setting After pressing and holding ENTER button for 2 seconds the unit will enter setting mode Press UP or DOWN button to select setting programs And then p...

Страница 29: ...age or the setting point in program 20 or solar and battery is not sufficient The battery energy will supply power to the load in the condition of theutility is unavailable or the battery voltage is h...

Страница 30: ...range will be between 90 and 280VAC UPS When selected the acceptable ac input voltage range will be between 170 and 280VAC GEN When the user uses the device to connect the generator select the generat...

Страница 31: ...ply the load or charge the battery it will NOT supply to the grid LBU Solar energy supplies power to the loads as the first priority If the battery voltage is lower than the set point in program 20 th...

Страница 32: ...RE Opnieuw opstarten inschakelen Program 09 inject to the grid not applicable Program 10 priority charging CSO Solar energy first Solar energy charges the battery as the first priority The utility pow...

Страница 33: ...m 13 set utility charging current Settings per system PB UPS 2 2 24 50A PB UPS 2 2 24 Li 50A PB UPS 3 5 24 50A PB UPS 3 5 24 Li 50A PB UPS 5 5 48 50A PB UPS 5 5 48 Li 50A PB UPS 10 10 48 100A PB UPS 1...

Страница 34: ...rogram 17 set bulk charging voltage PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 If user defined is selected in program 14 this program can be set The setting range is from 24 0V to 29 2V for 24Vdc model and 4...

Страница 35: ...set point regardless of the percentage of the load that is connected Program 20 switch from battery to utility discharge PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 Battery stops discharging voltage when gri...

Страница 36: ...page PTD If selected the display screen will stayat latest screen user finally switches Program 23 Backlight control LON backlight on LOF backlight off Program 24 alarm control BON alarm on BOF alarm...

Страница 37: ...working status SBD balancing solar power disable if selected the solar power input will be equal to the maximum charging capacity of the battery regardless of the number of consumers connected The ma...

Страница 38: ...available for 48V systems 57 6V These options do not apply to the PB UPS systems Program 32 not applicable Program 33 time battery equalization The setting range is from 5 minutes to 900 minutes The...

Страница 39: ...battery equalization will be activated immediately and EQ appears on the LCD main page If ADS is selected the equalization function will be canceled until the next activated equalization time starts...

Страница 40: ...V1 01 40 Programming via PC TOOL Main window when connected to live PB UPS via USB cable The main window shows the general operating status dashboard To access the settings login with default password...

Страница 41: ...configuration buttons appear all parameters were organized as Charger and Inverter inverter And there is a button to reset all current configurations to defaults Here are the parameters in 2 configur...

Страница 42: ...verter output voltage is high 07 Overload time out 08 Inverter bus voltage is too high 09 Bus soft start failed 11 Main relay failed 21 Inverter output voltage sensor error 22 Inverter grid voltage se...

Страница 43: ...under frequency 44 Inverter grid over frequency 51 Inverter over current protection error 52 Inverter bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery co...

Страница 44: ...Solar charger over temperature 76 PV charger communication error 77 Parameter error Beschrijving bedrijfsstatus Solar energy is higher than required power Solar energy is lower than required power Sol...

Страница 45: ...ery Off grid status energy comes from the battery The inverter stops working if you disconnect the inverter turns off with the soft key or if an error has occurred in the state in which it does not wo...

Страница 46: ...soidal utility or generator Nominal Input Voltage 230Vac Low Loss Voltage 90Vac 7V APL GEN 170Vac 7V UPS 186Vac 7V VDE Low Loss Return Voltage 100Vac 7V APL GEN 180Vac 7V UPS 196Vac 7V VDE High Loss V...

Страница 47: ...tage regulation batt mode 220Vac 240Vac adjustable efficiency peak 93 Transfer time 10ms UPS VDE 20ms APL AC input Voltage Vac 230 Adjustable voltage range 170 280 Vac for personal computers 90 280Vac...

Страница 48: ...00 298 468 125 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48 Low DC Warning Voltage At load 20 22 0Vdc 44 0Vdc 20 load 50 21 4Vdc 42 8Vdc At load 50 20 2Vdc 40 4Vdc Low DC Return Voltage Warning At load 20 23 0...

Страница 49: ...he battery is reversed Entry guard is activated 1 Check that the batteries and cables are connected properly 2 Recharge the battery 3 Replace the battery Mains power present but the device is running...

Страница 50: ...2 Internal temperature of inverter component is over 90oC Check whether the air flow of the unit is blocked or whether the ambient temperature is toohigh Fault code 03 Battery is over charged Return t...

Страница 51: ...tput voltage is unbalanced happens again please returnto repair center Fault code 56 Battery is not connected well or fuse is burnt If the battery is connected well please return to repair center Gesc...

Страница 52: ...2 Up to three units work together to support three phase equipment The maximum output power supported is 15kVA package contents Inside the box you will find the following items in the package Buildin...

Страница 53: ...tes the number of inverters connected in parallel Regarding net and load please also follow the same principle PAY ATTENTION Install the circuit breaker on the battery and mains side This will ensure...

Страница 54: ...inverters share the same battery bank Otherwise the inverters will switch to fault mode Parallel in mono phase setup PB UPS 10 10 48 Connection communication Inverter 1 set button 1 of the DIP switch...

Страница 55: ...d buttons 2 3 4 5 of the DIP switch in the upper position Inverter 2 set the button 2 of the DIP switch to the lowest position and the button 1 3 4 5 of the DIP switch in the top position Inverter 3 s...

Страница 56: ...button 1 3 of the DIP switch to the lower position and the buttons 2 4 5 of the the DIP switch in the upper position Inverter 2 set the button 2 3 of the DIP switch to the lower position and the butto...

Страница 57: ...eparately Fault reference code 80 CAN fault 81 Host loss 82 Synchronization loss 83 Battery voltage detected different 84 AC input voltage and frequency detected different 85 AC output current unbalan...

Страница 58: ...re connected to each other STEP 2 On the bottom panel of the inverter there are 5 pin DIP switches you can set it as follows in the figure below REMARK 1 If there are two inverters in parallel you onl...

Страница 59: ...en on SLAVE inverter STEP 5 When there is no more fault alarm the parallel system is fully installed STEP 6 Turn on all circuit breakers from the cabling to the load side This system will start supply...

Страница 60: ...lly Otherwise the AC icon will flash and they will not work in line mode LCD display in L1 LCD display in L2 LCD display in L3 STEP 5 When there is no more fault alarm the system is to support 3 phase...

Страница 61: ...ck the utility wiring connection and restart the inverter 85 AC output current unbalance Restart the inverter 86 AC output mode setting is different Turn off the inverter and check the DIP setting 87...

Страница 62: ...V1 01 62...

Страница 63: ...V1 01 63 PB SC12 170...

Страница 64: ...V1 01 64...

Страница 65: ...nt are defined as follows Danger that can cause serious injuries or even death Used to indicate potential danger it may cause death or serious injury if not avoided Used to indicate medium or low pote...

Страница 66: ...ulations before you start Pre Installation Requirements Only qualified persons with adequate training and familiar with all safety regulations may install operate or maintain PB SC 12 170 batteries In...

Страница 67: ...ce Modular design and installation for less space easy installation maintenance UL94 V0 ABS Container Integrating Gel and AGM technology there is no liquid electrolyte Oxygen recombination efficiency...

Страница 68: ...n 12 12Vdc 170 170Ah C10 2 0kWh energy at 100 discharge DOD100 at C10 1 3kWh energy at 60 discharge DOD60 at C10 C10 according to EUROBATNORM discharge at 10 of the Capacity 17A for 10 hours from 100...

Страница 69: ...m bulging Container Contains the electrolyte plates etc Keep the poisonous out and active material in so that the reaction could carry on Also it helps ventilation It is made from strong plastic mater...

Страница 70: ...25 Low selfdischarge The self discharge rate of LRC batteries is less than 3 of rated capacity at 20 25 storage temperature This low self discharge rate indicates a storage time under the aforementio...

Страница 71: ...The oxygen which is generated from the positive electrode will travel through the separators to the negative electrode to oxidize the Pb sohygrogen generation is controlled This recombination process...

Страница 72: ...discharge current the more the discharge capacity will be increased The larger the discharge current the lower the discharge capacity will be decreased C10 means the rated capacity discharged at 25 w...

Страница 73: ...arge curve the voltage will drop rapidly when it reaches critical and little energy can be harvest if we continue to discharge it will has some bad influence on the battery So the discharge must be st...

Страница 74: ...IFICATIONS Charge characteristic The figure below shows the constant charging characteristic the charging voltage increases with the charging time However at the final stage the charge voltage will in...

Страница 75: ...Storage time above 3 months or longer In battery group when the float charge voltage of one unit is below 2 16V Cell New battery is installed and debugged but not in operation model yet Float charge...

Страница 76: ...risk for fire and explosion so keep them away from fire heater or organic solvent Keep the batteries under dry cool environment when they are stored Please recharge the batteries using the instructio...

Страница 77: ...e produced in the battery negative plate this is called sulfate after they were stored for a long time Because lead sulfate is an insulator it will influence the performance of the charge therefore it...

Страница 78: ...increasewith the increasement of the temperature andcharge current The estimate battery float life can be judged by the standard high temperature accelerated life test The actual float life is affect...

Страница 79: ...he actual cycle life is depends on DOD and some other conditions ENVIRONMENT PROTECTION Toxic and poison Recycle This mark indicates that the product can not be classified with other waste In order to...

Страница 80: ...ontainer material ABS Nominal capacity 25 C 174Ah 10 uur 17 4A 1 80V cell 146 5Ah 5 uur 29 3A 1 75V cell 131 1Ah 3 uur 43 7A 1 75V cell Short circuit current 1706A Internal resistance 25 C 4 0m Temper...

Страница 81: ...V1 01 81 PB Li 12 100D...

Страница 82: ...V1 01 82...

Страница 83: ...attery Avoid short circuits as the terminals are always live avoid direct connection of the terminals to each other Do not place tools or objects on the battery Only extinguish with class D fire extin...

Страница 84: ...sposal LiFePO4 batteries should not be disposed of with household or commercial waste registered but must be handed in for disposal recycling at the collection points of the common take back system Th...

Страница 85: ...ages over lead acid batteries including lead acid AGM and GEL batteries and lithium batteries from other manufacturers Only about 40 50 of the weight of a lead acid battery of the same capacity Integr...

Страница 86: ...ther mobile applications Consumable battery or propulsion battery in boats emergency power supply BMS Battery Management System The Battery Management System integrated into every PowerBoozt LiFePO4 b...

Страница 87: ...urces Charge before use the battery is only charged to 40 60 during transport Series parallel connection PowerBoozt LiFePO4 batteries can be connected in series and or parallel note Before installatio...

Страница 88: ...he battery isolating switch to avoid to prevent discharge via hidden consumers If the battery is stored removed the terminals must be covered with a protective cap or be masked Ideal is storage in a d...

Страница 89: ...perature drops it automatically switches the battery back on The balancing of the cells is done automatically during loading or if necessary during a standby phase Discharging Discharge to 100 of capa...

Страница 90: ...name of the battery if assigned and the MAC address of the Bluetooth module By tapping your battery s MAC address You can find the MAC address of your battery on the small sticker on the battery make...

Страница 91: ...sed so far Congestion Indicators Green OK Red Error Overvoltage Under pressure Charging current too high Discharge current too high Temperature too low while charging Temperature too low when discharg...

Страница 92: ...V1 01 92 GRAPHS discharge graph Discharge with different currents at 25 C Discharge at different temperatures...

Страница 93: ...V1 01 93 Charging graph State of charge SOC with 0 5C at 25 C Charging characteristic with 0 5C at 25 C...

Страница 94: ...V1 01 94 Longevity and Self discharging graph Number of Cycles with 1C Self discharge at different temperatures...

Страница 95: ...the contrary Fully charge the battery to approx 60 80 and then disconnect or disconnect the battery from the vehicle In my vehicle it sometimes gets to 50 C and more in the summer Will it damage my l...

Страница 96: ...switch off the inverter However the maximum continuous discharge current of the battery must not be exceeded Can I extend lithium batteries with parallel connection of other batteries Yes provided th...

Страница 97: ...RANTY HANDLING All POWERBOOZT batteries are manufactured according to the strictest quality criteria and POWERBOOZT guarantees that the LiFePO4 batteries are delivered in perfect condition POWERBOOZT...

Страница 98: ...uick handling If possible use the original packaging as a shipping box If you no longer have the original packaging make sure you have enough protection against transport damage with suitable UN certi...

Страница 99: ...continuous discharge current 100A Peak discharge current 200A 4 5 seconds 2 5seconds BMS shutdown on discharge 250A 50A Recommended Shutdown 11V Back on 11 2V Charge Recommended charging current 50A M...

Страница 100: ...V1 01 100...

Страница 101: ...V1 01 101 LfeLi 48100TB...

Страница 102: ...V1 01 102...

Страница 103: ...in this document are defined as follows Danger that can cause serious injury or even death Used to indicate potential danger could be death or serious cause injury if not avoided Used to indicate medi...

Страница 104: ...ormance Battery with respect for safety and environment that can be used in harsh outdoor environments The system also includes an advanced Battery Management System BMS which is responsible is for ma...

Страница 105: ...V1 01 105 Product structure LFeLi frontpanel...

Страница 106: ...of the battery via light indicator Capacity 75 100 50 75 25 50 0 25 indication for on indication for out ALM RUN RUN en ALM indicates battery status Function interpretation color blink frequency Indi...

Страница 107: ...Pack2 OFF OFF ON OFF 4 PACK3 Use as SlavePack3 ON OFF ON OFF 5 PACK4 Use as SlavePack4 OFF ON ON OFF 6 PACK5 Use as SlavePack5 ON ON ON OFF 7 PACK6 Use as SlavePack6 OFF OFF OFF ON 8 PACK7 Use as Slav...

Страница 108: ...module can see a unit with any address but a single unit can be seen with RS232 not all units in the package Software and manual are supplied with the unit on a CD RS485 When the system is in parallel...

Страница 109: ...rge and discharge over low temperature OUTPUT exit A total of 4 output terminals 2 positive and 2 negative marked P P Each clamp has the specification for M8 Stud Required Torque Settings 6 1N 7 5N MC...

Страница 110: ...nu keys The functions are described below Display function keys Main menu Confirm enter Page up Page down Return launch Operating procedures 1 Press once the LCD screen lights up and the welcome inter...

Страница 111: ...Then click again to go to the main menu bar 3 Scroll page up and page down go to it Menu screen when the arrow points to the corresponding bar press Enter to to confirm 4 Go back to the menu bar and...

Страница 112: ...to add new features or fix a bug POWERBOOZT provides the software to upgrade the battery firmware When upgrade first make sure the BMS product is in standby state Please switch off charger and consume...

Страница 113: ...the button Upgrade to perform the upgrade After opening the upgrade tool the first upgrade will ask The upgrade is complete Are you sure you want to upgrade Click OK to continue the upgrade and there...

Страница 114: ...ng overcurrent the discharge change from charge to discharge and vice versa The monitoring module monitors the equilibrium function and the power the temperature and the SOC The control module transmi...

Страница 115: ...ransportation the battery may enter sleep mode to avoid the loss of capacity to decrease Easily accessible front connectors to facilitate installation of one or more units Lightweight convenient size...

Страница 116: ...e management parameters and the output parameters of the switching power system INSTALLATION GUIDE Installation Precautions Comply with local laws and regulations Be sure to follow local laws and regu...

Страница 117: ...e safety of the system and personnel 2 fire protection No flammable explosive or other dangerous goods may be stored in the room and the room must be equipped with effective fire equipment such as CO2...

Страница 118: ...ll the module in dusty dirty environments Do not place any objects on top of the lithium ion battery People should never be on the battery sit or stand Check power Before installation check the load c...

Страница 119: ...sories are shipped in cardboard or wooden boxes When unpacking be careful when disassembling Check that the device and accessories correspond to the packing list and that nothing during the shipment w...

Страница 120: ...Measuring tape Drilling machine Gereedschap voor levering en uitpakken Manual Forklifts Electric Forklift support ring weight 400kg Leverage weight 400kg Electrical installation tools Insulated gloves...

Страница 121: ...attery and turn off the rectifier without plugging in the mains to switch The battery must be recharged for normal operation Standard installation of the cabinet Mounting These units are suitable for...

Страница 122: ...sed Before parallel installation set the battery to limited charge mode Please refer to for detailed operations the software manual To ensure the longest possible life of the lithium ion battery pack...

Страница 123: ...thly Environment Keep away from heat sources and avoid direct sunlight Visual inspection In case of breakage leakage or deformation isolate the problematic battery and contact your installer quarterly...

Страница 124: ...Step 1 Check the LEDs to determine which part is faulty Step 2 Check the information in case of failure in the monitoring module Step 3 Classify the information DC AC modules batteries control etc St...

Страница 125: ...rm disappears replace the module Voltage to low No AC power Check the DC undervoltage alarm point default value is 45V If it is not reasonable please adjust it according to the actual situation Alarm...

Страница 126: ...ithin an acceptable range address the interference from the temperature control system When the temperature in the system cabinet returns to the normal range turns off the alarm automatically The temp...

Страница 127: ...sensor is defective If yes replace the temperature sensor Battery temperature is too low Battery temperature is set too low alarm point Check if the battery temperature is too low default 0 If yes ad...

Страница 128: ...e voltage Default value Maximum value 48 100 40 5 20 100 Parameters for charging multiple modules in parallel Voltage V Capacity Ah Charge voltage limit V Maximum current A nota minimum value Default...

Страница 129: ...index 0 1C charging performance Discharge time 600min Standard battery charge 1h within 1h with 0 1C discharge current at 40 5V record the discharge time 0 5C discharge performance Discharge time 115...

Страница 130: ...s a green product It should be recycled and not thrown away Recyclage This mark indicates that the product should not be disposed of with other types of waste To prevent potentially hazardous substanc...

Страница 131: ...efficiency Environmentally friendly without heavy metals Complete with built in Battery Management System BMS Can use most standard VRLA chargers for this system Low self discharge rate of 2 years be...

Страница 132: ...an 20 years Cycle Life Over 3500 cycles at 100 discharge IP class IP31 Casing material Black lacquered steel cabinet Temperature at charging 0 tot 55 C At discharging 20 tot 60 C At storage 20 tot 60...

Страница 133: ...22 0 17 423 2 482 6 0 10 40 85 01 0 21 335 5 382 6 0 9 27 67 43 0 26 266 2 303 5 0 8 25 53 49 0 33 211 1 240 7 1 7 35 42 41 0 42 167 4 190 9 2 6 54 33 62 0 53 132 7 151 3 3 5 83 26 67 0 66 105 2 120 0...

Страница 134: ...ry must be installed in a suitable place 3 Connect each connector in turn to each of the output ends of the lithium ion battery pack Connect all lithium ion batteries to the positive terminals first t...

Страница 135: ...V1 01 135 3 Loosen the screws from the front panel and from the bottom plate 4 Open the front panel and bottom plate 5 Remove the BMS sample leads from the sockets in the following order 4 3 2 1...

Страница 136: ...V1 01 136 7 Install the BMS sample cables from the receptacles in the following order 1 2 3 4 7 Install the front panel plate and fastener Reset the battery by pressing the reset button for 6 seconds...

Страница 137: ...V1 01 137 APPENDIX...

Страница 138: ...V1 01 138...

Страница 139: ...V1 01 139 COMPOSITION AND SETTINGS SYSTEMS PB UPS 2 2 24...

Страница 140: ...eyes 1 x PB CABR2 35M10 red cale 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB 5093300 MEGA fuseholder 1 x PB 5097349 2 MEGA fuses 250A 32V 1 x PB SC12...

Страница 141: ...V1 01 141 PB LSC 1 PB SC12 170 PB UPS 2K24...

Страница 142: ...V1 01 142...

Страница 143: ...V1 01 143 PB UPS 3 5 24...

Страница 144: ...e 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 2 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10 cable eyes 1 x PB 5093300 MEGA fuseholder 1 x PB 5097349 2...

Страница 145: ...V1 01 145 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...

Страница 146: ...V1 01 146 PB UPS 3K24 dimensions in mm...

Страница 147: ...V1 01 147 PB UPS 5 5 48...

Страница 148: ...eyes 1 x PB CABR2 50M10 red cable 2m 50mm with M10 cable eyes 1 x PB CABB3 50M10 black cable 3m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB 5097557 2 ANL fuses 250A 32V 4 x PB SC12...

Страница 149: ...V1 01 149 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...

Страница 150: ...V1 01 150 PB UPS 5K48 dimensions in mm...

Страница 151: ...V1 01 151 PB UPS 10 10 48...

Страница 152: ...M10 cable eyes 1 x PB CABR2 70M10 red cable 2m 70mm with M10 cable eyes 1 x PB CABB1 70M10 black cable 70mm with M10 cable eyes 1 x PB CABR1 70M10 red cable 70mm with M10 cable eyes 1 x PB 5073550 ANL...

Страница 153: ...V1 01 153...

Страница 154: ...V1 01 154 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...

Страница 155: ...V1 01 155 PB UPS 5K48 dimensions in mm...

Страница 156: ...V1 01 156 PB UPS 15 15 48...

Страница 157: ...M10 cable eyes 1 x PB CABR2 95M10 red cable 2m 95mm with M10 cable eyes 2 x PB CABB1 95M10 black cable 95mm with M10 cable eyes 2 x PB CABR1 95M10 red cable 95mm with M10 cable eyes 1 x PB 5073550 ANL...

Страница 158: ...V1 01 158...

Страница 159: ...V1 01 159 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...

Страница 160: ...V1 01 160 PB UPS 5K48 dimensions in mm...

Страница 161: ...V1 01 161 PB UPS 2 2 24 Li...

Страница 162: ...yes 1 x PB CABR2 35M10 red cable 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10 cable eyes 1 x PB 5093300 ME...

Страница 163: ...V1 01 163 PB LSC 1 PB Li 12 100D...

Страница 164: ...V1 01 164 PB UPS 2K24...

Страница 165: ...V1 01 165 PB UPS 3 5 24 Li...

Страница 166: ...le 2m 35mm with M10 cable eyes 1 x PB CABB3 35M10 black cable 3m 35mm with M10 cable eyes 1 x PB CABB1 35M10 black cable 1m 35mm with M10 cable eyes 2 x PB CABB0 3 35M10 black cable 0 3m 35mm with M10...

Страница 167: ...V1 01 167 PB LSC 1 PB Li 12 100D...

Страница 168: ...V1 01 168 PB UPS 2K24...

Страница 169: ...V1 01 169 PB UPS 5 5 48 Li...

Страница 170: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABR2 50M10 red cable 2m 50mm with M10 cable eyes 1 x PB CABB3 50M10 black cable 3m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB 5...

Страница 171: ...V1 01 171 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Страница 172: ...V1 01 172 PB UPS 5K48 dimensions in mm...

Страница 173: ...V1 01 173 PB UPS 10 10 48 Li...

Страница 174: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABB2 70M10 black cable 2m 70mm with M10 cable eyes 2 x PB CABB1 50M10 black cable 1m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB...

Страница 175: ...V1 01 175 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Страница 176: ...V1 01 176 PB UPS 5K48 dimensions in mm...

Страница 177: ...V1 01 177 PB UPS 15 15 48 Li...

Страница 178: ...1 50M10 red cable 1m 50mm with M10 cable eyes 1 x PB CABB2 95M10 black cable 2m 95mm with M10 cable eyes 3 x PB CABB1 50M10 black cable 1m 50mm with M10 cable eyes 1 x PB 5073550 ANL fuseholder 1 x PB...

Страница 179: ...V1 01 179 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...

Страница 180: ...V1 01 180 PB UPS 5K48 dimensions in mm...

Страница 181: ...MEASURES Install this product only in a dry environment To avoid the risk of fire only use correctly dimensioned cables which are suitable for the expected flows in your installation To avoid damage t...

Страница 182: ...od The cables for the smaller loads can then be attached to the bolts further away from them to be mounted CHARACTERISTICS High purity tinned copper base plates ensure optimum electrical conductivity...

Страница 183: ...V1 01 183 ANL MEGA...

Страница 184: ...event excessive mechanical stress on the fuse holder CHARACTERISTICS High purity tinned copper base plates ensure optimum electrical conductivity Optimal corrosion resistance by using stainless steel...

Страница 185: ...of the Wi Fi plug 14 with the inverter and insert the plug firmly in touch Secure the Wi Fi plug 14 to the inverter with the screw Check the status of the LED indicator when you see the orange LED li...

Страница 186: ...e and download the APP Open the APP tap the Wi Fi Config button to enter this page Tap the Connect Wi Fi Data Logger button on the connected page For Android phones this one is Step not necessary Sele...

Страница 187: ...lished tap the Network Setting button Enter the information according to the prompts to complete the network setup Reconnect the Wi Fi Open the APP tap the Register Register button Complete account cr...

Страница 188: ...tion Add multiple Dataloggers Note One account can create multiple systems and one system can create multiple data loggers to add If you only have one datalogger you can skip this last step Tap the ne...

Страница 189: ...V1 01 189 Finally Note In addition to the SmartClientApp you can also monitor your installations remotely with the mini program WeChat...

Страница 190: ...V1 01 190...

Страница 191: ...V1 01 191...

Страница 192: ...V1 01 192...

Отзывы: