V1.01
31
Program 05
–
Solar energy delivery priority
BLU
Solar energy provides power to charge the battery as the first priority.
When the utility is available, if the battery voltage is lower than the set point in program 21, the solar
will never deliver to the load or feed into the grid, only charge the battery.
If the battery voltage is higher than the set point in program 21, the solar will supply the load or charge
the battery
–
it will
NOT
supply to the grid.
LBU
Solar energy supplies power to the loads as the first priority.
If the battery voltage is lower than the set point in program 20, the solar energy will never feed to the
load or feed into the grid, only charge the battery.
If the battery voltage is higher than the set point in program 20, the solar will supply the load or charge
the battery
–
it will
NOT
supply to the grid.
Program 06
–
Bypass
Overload Bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode
BYD
Bypass disable
BYE
Bypass enable
Содержание LfeLi-48100TB
Страница 10: ...V1 01 10...
Страница 11: ...V1 01 11 PB UPS 2K24 PB UPS 3K24 PB UPS 5K48...
Страница 12: ...V1 01 12...
Страница 62: ...V1 01 62...
Страница 63: ...V1 01 63 PB SC12 170...
Страница 64: ...V1 01 64...
Страница 81: ...V1 01 81 PB Li 12 100D...
Страница 82: ...V1 01 82...
Страница 92: ...V1 01 92 GRAPHS discharge graph Discharge with different currents at 25 C Discharge at different temperatures...
Страница 93: ...V1 01 93 Charging graph State of charge SOC with 0 5C at 25 C Charging characteristic with 0 5C at 25 C...
Страница 94: ...V1 01 94 Longevity and Self discharging graph Number of Cycles with 1C Self discharge at different temperatures...
Страница 100: ...V1 01 100...
Страница 101: ...V1 01 101 LfeLi 48100TB...
Страница 102: ...V1 01 102...
Страница 105: ...V1 01 105 Product structure LFeLi frontpanel...
Страница 137: ...V1 01 137 APPENDIX...
Страница 138: ...V1 01 138...
Страница 139: ...V1 01 139 COMPOSITION AND SETTINGS SYSTEMS PB UPS 2 2 24...
Страница 141: ...V1 01 141 PB LSC 1 PB SC12 170 PB UPS 2K24...
Страница 142: ...V1 01 142...
Страница 143: ...V1 01 143 PB UPS 3 5 24...
Страница 145: ...V1 01 145 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...
Страница 146: ...V1 01 146 PB UPS 3K24 dimensions in mm...
Страница 147: ...V1 01 147 PB UPS 5 5 48...
Страница 149: ...V1 01 149 PB LSC 1 dimensions in mm PB SC12 170 dimensions in mm...
Страница 150: ...V1 01 150 PB UPS 5K48 dimensions in mm...
Страница 151: ...V1 01 151 PB UPS 10 10 48...
Страница 153: ...V1 01 153...
Страница 154: ...V1 01 154 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...
Страница 155: ...V1 01 155 PB UPS 5K48 dimensions in mm...
Страница 156: ...V1 01 156 PB UPS 15 15 48...
Страница 158: ...V1 01 158...
Страница 159: ...V1 01 159 PB LSC 2 dimensions in mm B SC12 170 dimensions in mm...
Страница 160: ...V1 01 160 PB UPS 5K48 dimensions in mm...
Страница 161: ...V1 01 161 PB UPS 2 2 24 Li...
Страница 163: ...V1 01 163 PB LSC 1 PB Li 12 100D...
Страница 164: ...V1 01 164 PB UPS 2K24...
Страница 165: ...V1 01 165 PB UPS 3 5 24 Li...
Страница 167: ...V1 01 167 PB LSC 1 PB Li 12 100D...
Страница 168: ...V1 01 168 PB UPS 2K24...
Страница 169: ...V1 01 169 PB UPS 5 5 48 Li...
Страница 171: ...V1 01 171 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Страница 172: ...V1 01 172 PB UPS 5K48 dimensions in mm...
Страница 173: ...V1 01 173 PB UPS 10 10 48 Li...
Страница 175: ...V1 01 175 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Страница 176: ...V1 01 176 PB UPS 5K48 dimensions in mm...
Страница 177: ...V1 01 177 PB UPS 15 15 48 Li...
Страница 179: ...V1 01 179 LfeLi48100T dimensions in mm PB LSC Li dimensions in mm...
Страница 180: ...V1 01 180 PB UPS 5K48 dimensions in mm...
Страница 183: ...V1 01 183 ANL MEGA...
Страница 190: ...V1 01 190...
Страница 191: ...V1 01 191...
Страница 192: ...V1 01 192...