Operation and installation manual
Page 75 of 82
(PVI-10.0/12.5-OUTD-xx Rev:1.2)
8.2
Output values
Description
Value
PVI – 10.0-OUTD-xx
Value
PVI – 12.5-OUTD-xx
Nominal output
power
10000 W
12500 W
Grid voltage
maximum operating
range
(2)
from 326 Vrms to 456 Vrms phase-phase
from 188 Vrms to 263 Vrms phase-neutral
Grid voltage
nominal
400 Vrms phase-phase
230 phase-neutral
Grid frequency,
maximum range
from 47 to 63 Hz
Grid frequency,
nominal
50 Hz
Grid frequency,
operating range
according to
DK5940 standard
from 49.72 to 50.28 Hz
Nominal output
current per phase
14.5 Arms
18.1 Arms
Max. output current
per phase
16.6 Arms
20 Arms
Output Overcurrent
Protection
19 Arms
22 Arms
(2)
Depending on nominal voltage selected (using a password protected menu) the
minimum operating voltage could reach 311 Vrms phase-phase or 180 Vrms phase-
neutral.