Operation and installation manual
Page 30 of 82
(PVI-10.0/12.5-OUTD-xx Rev:1.2)
WARNING
: In some cases the system could consist of one array only.
In such a case, if array power output is lower than maximum capacity of one
AURORA section (see specifications chart) and if array current capacity is
below 18 Adc, the array could be connected just to IN1 section.
To avoid any problems when assessing panels electric insulation features, it is
recommended to short-circuit the inputs of the second section (IN2), by
connecting a cable to the relevant terminals inside inverter board, as shown in
Fig. 13. To gain access to the board you shall remove the panel on Aurora
front
Fig.12 - Connections available on a brand new unit