POWER ELECTRONICS
ETHERNET GATEWAY
INSTALLATION AND CONNECTION
29
E
N
G
L
I
S
H
3.3.7.
Medium voltage variable speed drive XMV660 Series
To realize the connection between the Ethernet gateway and the
drive a Male 8 pin mini DIN SubD connector must be used.
Figure 3.14 XMV660
– Ethernet Gateway connection
Once the device is connected, set the following parameters as
follows:
Description
Setting
Modbus Device Address
1
In XMV660 drives this parameter cannot be set.
Modbus Communication
Baud Rate
9600
9600bps
Modbus Communication
Parity
Even
In XMV660 drives this parameter cannot be set.