POWER ELECTRONICS
ETHERNET GATEWAY
ETHERNET GATEWAY CONFIGURATION
33
E
N
G
L
I
S
H
MODBUS
register
MODBUS_COMM_BAUDRATE
[MODBUS
Address: 40415] is allocated to switch over different baud rates.
MODBUS Address: 40415
Selected Baud Rates
0
600 BAUDS
1
1200 BAUDS
2
2400 BAUDS
3
4800 BAUDS
4
9600 BAUDS
5
19200 BAUDS
The Users are free to change the baud rates at any time. But it will
come into effect only after the hard reset of the gateway. The default
baud rate is 9600 BAUDS.
4.4.3.
MODBUS/RTU Communication Parity
The Ethernet Gateway supports 3 different parity values for the
MODBUS/RTU communication.
MODBUS register MODBUS_COMM_PARITY [MODBUS Address:
40416] is allocated to switch over different parity values.
MODBUS Address: 40416
Selected PARITY
0
ODD
1
NONE
2
EVEN
4.5.
Serial Slave Response Timeout
MODBUS
register
“SERIAL_SLAVE_RESPONSE_TIMEOUT”
[MODBUS Address: 41501] is allocated to configure the timeout value
between the slave and the Ethernet Gateway while the serial
communication is in progress. The Users are free to change this
timeout value at any time. The default serial slave response time out
value is 10ms.
Содержание GBC05CI
Страница 1: ...PASARELAETHERNET ETHERNET GATEWAY Ethernet Gateway Communication Network...
Страница 2: ......
Страница 3: ...Communication Network Ethernet Gateway Edition April 2012 GBC05CI Rev C...
Страница 4: ...ETHERNET GATEWAY POWER ELECTRONICS 2...
Страница 6: ...ETHERNET GATEWAY POWER ELECTRONICS 4...
Страница 20: ...ETHERNET GATEWAY POWER ELECTRONICS 18 INSTALLATION AND CONNECTION Figure 3 5 Location of the LEDs...
Страница 43: ...POWER ELECTRONICS ETHERNET GATEWAY WEB SERVER CONFIGURATION 41 E N G L I S H...
Страница 45: ...www power electronics com...