POWER ELECTRONICS
ETHERNET GATEWAY
INSTALLATION AND CONNECTION
19
E
N
G
L
I
S
H
3.3.
Connection for Equipments of Power
Electronics
The Ethernet Gateway supports the following Modbus slaves:
Variable Speed Drive of SD700 Series.
Variable Speed Drives of SD100, SD250 and SD450 Series.
Digital Soft Starter of V5 Series.
Medium Voltage Soft Starter of VS65 Series.
Medium Voltage Variable Speed Drive of XMV660 Series.
Note:
To connect other slaves, contact with Power Electronics.
Finally, also the parameters related to the Modbus communication can
be configured:
Transmission Speed (Baud rate)
Exceeded Time (Time out)
Stop bit
Parity bit
Retries
3.3.1.
Variable Speed Drives of SD100 Series
When using the Ethernet Gateway with SD100 drive, the last one
must have an optional board MODBUS-RTU SD100. All
requirements relative to the installation can be found in the user
manual provided with the optional board.
General specifications:
Transmission form:
Bus method, Multi drop Link System.
Applicable drive:
SD100.
Connectable drives:
Maximum 31.
Transmission distance:
Below 1.200m maximum (700m recommended).
Cable recommended:
0.75mm² (18AWG), Shielded twisted pair.
Installation:
GN, N and P terminals
Power supply:
Power supply insulated from the inverter power supply.
Содержание GBC05CI
Страница 1: ...PASARELAETHERNET ETHERNET GATEWAY Ethernet Gateway Communication Network...
Страница 2: ......
Страница 3: ...Communication Network Ethernet Gateway Edition April 2012 GBC05CI Rev C...
Страница 4: ...ETHERNET GATEWAY POWER ELECTRONICS 2...
Страница 6: ...ETHERNET GATEWAY POWER ELECTRONICS 4...
Страница 20: ...ETHERNET GATEWAY POWER ELECTRONICS 18 INSTALLATION AND CONNECTION Figure 3 5 Location of the LEDs...
Страница 43: ...POWER ELECTRONICS ETHERNET GATEWAY WEB SERVER CONFIGURATION 41 E N G L I S H...
Страница 45: ...www power electronics com...