MAN-230000-00 REV B
57
Charge Timers Screen
The
CHARGE TIMERS
screen is used to view and modify the timers for each
charge mode.
Parameter
Description
Defaults
1
Total Timer
The total timer sets the maximum duration of
a charge cycle.
Range: 0
–12:00 hrs
9:00 hrs
2
Trickle Timer
The trickle timer sets the maximum duration
of a trickle charge phase. This timer is
not
included in the total timer duration.
Range: 0
–12:00 hrs
12:00 hrs
3
CC Charge Timer
The constant current timer sets the maximum
duration of a constant current charge phase.
Range: 0
–12:00 hrs
3:00 hrs
4
CV Charge Timer
The constant voltage timer sets the maximum
duration of a constant voltage charge phase.
Range: 0
–12:00 hrs
3:00 hrs
5
Finish dV
Sets dV in mV/cell for the finish termination
condition. If the VPC does not change by this
amount in the specified dt time, the finish
mode will be terminated.
Range: 1
–200 mV
5 mV/cell
6
Finish dt
Sets dt in minutes for the finish termination
condition.
Range: 1
–120 min
25 min
7
Finish Timer
The finish charge timer sets the maximum
duration of a finish charge phase.
Range: 0
–12:00 hrs
3:00 hrs
8
Equalize Timer
The equalize timer sets the maximum
duration of an equalize charge phase. This is
not
included in the total timer duration.
Range: 0
–12:00 hrs
6:00 hrs
9
High Pulse Time
DO NOT CHANGE DEFAULT VALUE!
60 sec
10 Zero Pulse Time
DO NOT CHANGE DEFAULT VALUE!
1 sec