MAN-230000-00 REV B
18
Getting Started
The LCD display on the
PowerCharge™ iHF3
series presents various screens and
SCREEN MESSAGES
.
1. Powering the Charger
a. Energize the AC mains.
b. Turn the AC disconnect switch to the
ON
position.
c. Verify that the LCD display is lit and displays the
CONNECT BATTERY
screen. The LCD displays the battery voltage setting and the maximum
current setting on the first line (e.g., 48 V and 200 A).
0 4 8 V 2 0 0 A
0 4 / 1 5 / 2 0 1 1 1 2 : 0 0 : 0 0
C O N N E C T B A T T E R Y
D I S P L A Y
d. If the LCD is not lit, or if the message is not displayed, cycle the switch to the
OFF
position and then return it to the
ON
position.
DANGEROUS VOLTAGES AND CURRENTS ARE PRESENT IN THE AC
MAINS WHEN ENERGIZED. ONLY TRAINED PERSONNEL SHOULD
PERFORM THESE CHECKS, USING PROPER EQUIPMENT AND
PROCEDURES.
e. If the charger still does not power up, carefully verify the source circuit and
wiring to the charger and correct any problems. Check that the fuses in the
AC mains junction box on the wall are intact, and that the supply voltage for
all three phases (AC mains line-to-line) is 400 V
–480 V ± 10%, and matches
to 10 VAC or better.
f. Restart the charger; if the problem persists, contact the dealer or Power
Designers USA LLC.
WARNING