MAN-230000-00 REV B
35
5. Over Temperature Ambient
C H A R G E R S T O P P E D :
A M B I E N T
O V E R T E M P E R A T U R E
E X I T
Possible Causes
Dirty air filter
Blocked air flow to the charger
Failed cooling fan
Room temperature above 104
˚F
Troubleshooting
a. Select
STOP
to revert to the
IDLE MODE
screen.
b. Allow the charger to cool down.
c. Make sure there are no airflow restrictions at the front or the rear of the
charger chassis.
d. Check the air filter and clean if necessary.
e. Restart the charge cycle by selecting
START
.
f. If the fault persists, contact the dealer or Power Designers USA LLC.