MAN-230000-00 REV B
52
System Settings Screens
SYSTEM SETTINGS
screens are used to view and modify various charger options
and system parameters.
Parameter
Description
Defaults
First screen
1
Present Date
Today’s date.
Manuf.
date
2
Present Time
Present time.
CST
3
Cells Autodetect
Autodetect battery nominal voltage (# of cells)
—
YES or NO. If NO is selected, the charger is set
for single voltage operation.
YES
4
Charge Autostart
Autostart charger upon connecting a battery
—
YES or NO.
NO
5
Temp Format
Temperature display
—°C or °F.
Fahrenheit
6
Daylight Savings
Automatically adjust for daylight time saving
—
YES or NO.
YES
7
Active Profile
Default profile to be activated
—Profile 0 or Profile
1.
Profile 0
8
Profile
Autoswitch
Automatically switch between Profile 0 and Profile
1 once the start day and time of Profile 1 are
reached
—YES or NO.
YES
Second screen
1
Precharge High
The high voltage limit of the precharge function.
Range: 12.0
–60.0 V
50V
2
Precharge Low
The low voltage limit of the precharge function.
Range: 12.0
–60.0 V
40V
3
Precharge Idle
Precharge is enabled
—YES or NO.
NO
4
Equalize Mode
Termination condition for the equalization charge
phase
—Timer Limit or CV Limit.
Timer
Limit
5
Use PT Params
Using the
PowerTrac™SP+
with 485 Comm
—
YES or NO.
No
6
Ignore PT Faults
Prevent the
PowerTrac™SP+
from disabling the
charger on a
PowerTrac™
fault
—YES or NO.
No
7
Delay Start
Timer
Set time delay to start charger after battery
cooldown.
0 min