MAN-230000-00 REV B
39
9. Charger Timeout Faults
C H A R G E R T I M E O U T :
X X X X X X X X X X X X T I M E R
E X I T
The
XXXXXXXX
field
indicates which timer has caused the problem:
TOTAL
CHARGE
,
TRICKLE CHARGE
,
CC CHARGE
,
CV CHARGE
,
or
FINISH
CHARGE TIMER
.
Possible Causes
Programmed charge timers are set incorrectly
Programmed charge parameters are set incorrectly
Battery has shorted cell(s)
Troubleshooting
a. Select
STOP
to revert to the
IDLE MODE
screen.
b. Start the
PowerCharge User
software provided for use with Palm, Pocket
PC, PC, or Netbook, select the
Charge Timers
button and select the
Scan
button on the
CHARGE TIMERS
screen.
c. Verify that the programmed timer values are correct. If not, reset as
appropriate.
d. Using the provided software, start the
PowerCharge User
program, select
Charge Parameters
and then select the
Scan
button on the
CHARGE
PARAMETERS
screen.
e. Verify that the programmed parameters values are correct. If not, reset as
appropriate.
f. Verify that the battery is in good working condition (i.e., no shorted cells).