MAN-230000-00 REV B
28
Selecting
/
sets the recovery charge current setting in the range of 10 A to
60 A in 5 A increments. Recommended recovery charge current setting is 5
A/100 Ahrs (5% of rated capacity).
See Appendix D, page 66 of this
manual, for instructions on how to determine the recovery charge
current and timer setting.
d. Select the correct value, and then select
ENT
. The
RECOVERY CYCLE
TIMER
screen appears.
R E C O V E R Y C Y C L E
T I M E R
1 2 : 0 0
E X I T E N T E R
Selecting
/
allows adjustment of the charge timer setting in 15-minute
increments. The charge timer setting must be less than 24 hours. Select the
desired value then select
ENT
. The
PUSH START TO BEGIN
RECOVERY
screen appears.
P U S H S T A R T
T O B E G I N R E C O V E R Y
E X I T
e. Push
START
to initiate the recovery cycle. Once the cycle is complete, a
CYCLE COMPLETE
message appears.
NOTE: The recovery cycle is a separate cycle; activating it does not affect
other charger settings.