Manual No. 405/0101
LIGHTING INSTRUCTIONS
29
8. LIGHTING INSTRUCTIONS - PAGE 29
See section 4.1 for boiler controls.
For access to the controls open the control panel cover (hinges down), if the internal programmer is fitted lower the
left hand cover after first opening the right hand one.
If a programmer is fitted refer to Programmer instructions to set the programmer.
Do not
attempt to light the boiler if the system pressure (see pressure gauge) is less than 0.5 bar. Repressurise the system
to 1.5 bar (see section 2.11, paragraph 4) and check for leaks, rectifying where necessary.
With the gas supply on and the electricity supply off.
1.
Turn the boiler thermostat control knob to 0.
2.
Switch on the electricity supply, set the programmer to continuous, if a programmer is fitted and check that all system
controls are calling for heat.
3.
Turn the boiler thermostat to 7. The automatic ignition sequence will start. The fan will start and after a purge period of
about 10 seconds a click will be heard indicating that the start gas solenoid has opened, the ignition sparks will also be
heard. The pilot will light and after a second or so the main gas solenoid will open and the main burner will light.
An amber neon, positioned between the pressure gauge and boiler thermostat, will light whenever the main burner is
alight.
Note:
The pilot burner is turned off every time the main burner is off. The ignition sequence is automatically activated
when the boiler thermostat requires heat.
4.
If a programmer is fitted, ensure that the timer is set to the correct time and the programme is set to the required
settings.