Configuration of extension modules
Prog. no.
Level Standard value
Relay output QX22 module 1
See
Parameters see Relay output QX21 module 1 (prog. no.
7301)!
7302
C
None
Relay output QX23 module 1
See
Parameters see Relay output QX21 module 1 (prog. no.
7301)!
7303
C
None
Sensor input BX21 module 1
None | Hot water sensor B31 | Collector sensor B6 | HW circulation sensor B39
| Buffer sensor B4 | Buffer sensor B41 | Common flow sensor B10 | Solid fuel
boiler sensor B22 | HW charging sensor B36 | Buffer sensor B42 | Schienen
rücklauffühler B73 | Cascade return sensor B70 | Swimming pool sensor B13 |
Solar flow sensor B63 | Solar return sensor B64
7307
C
None
Sensor input BX22 module 1
See
Parameters see Relay output QX21 module 1 (prog. no.
7307)!
7308
C
None
Function input H2 module 1
None | Optg mode change CHs+HW | Optg mode changeover HW | Optg mode
changeover CHs | Optg mode changeover CH1 | Optg mode changeover CH2 |
Optg mode changeover CH3 | Heat source block | Error/alarm message |
Consumer request VK1 | Consumer request VK2 | Release swimpool source
htg | Excess heat discharge | Release swi pool solar | Operating level HW |
Operating level CH1| Operating level CH2| Operating level CH3 | Room
thermostat CH1| Room thermostat CH2| Room thermostat CH3 | Trinkwasser
thermostat | Limit thermostat HC | Start prevention | Consumer request VK1
10V | Consumer request VK2 10V | Leistungsanforderung 10V
7311
C
None
Contact type H2 module 1
NC | NO
7312
E
NO
Voltage value 1 H2 module 1
7314
E
0.5
Funct value 1 H2 module 1
7315
E
0
Voltage value 2 H2 module 1
7316
E
10
Funct value 2 H2 module 1
7317
E
1000
Function input H21 module 1
None | Optg mode change CHs+HW | Optg mode changeover HW | Optg mode
changeover CHs | Optg mode changeover CH1 | Optg mode changeover CH2 |
Optg mode changeover CH3 | Heat generation lock | Error/alarm message |
Consumer request VK1 | Consumer request VK2 | Release swimpool source
htg | Übertemperaturableitung | Release swi pool solar | Operating level HW |
Operating level CH1 | Operating level CH2 | Operating level CH3 | Room
thermostat CH1 | Room thermostat CH2 | Room thermostat CH3 | Circulating
pump thermostat | Pulse count | Boiler return thermostat| Flow measurement Hz
| Consumer request VK1 10V | Consumer request VK2 10V | Room temp 10V
7321
C
Optg mode change
CHs+HW
Contact type H21 module 1
NC | NO
7322
C
NO
Input value 1 H21 module 1
7324
C
0
Funct value 1 H21 module 1
7325
C
0
Input value 2 H21 module 1
7326
C
10
Funct value 2 H21 module 1
7327
C
100
Funct input EX21 module 1
None | Counter 1st burner stage | Heat generation lock | Error/alarm message |
Excess heatdischarge
7342
C
None
9 Settings
74
7636047 - 02 - 24082015
Содержание eurocondense four 125 kw
Страница 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Страница 39: ...5 5 2 Legend Fig 21 Legend for application examples part 1 5 Before installation 7636047 02 24082015 39 ...
Страница 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Страница 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Страница 146: ...Index 146 7636047 02 24082015 ...
Страница 148: ...7636047 02 24082015 ...