Heating circuit 3
Heating circuit 2
Heating circuit 1
3
Heating circuit pump, mixer
03 Heating circuit pump, mixer
03 Heating circuit pump, mixer
Software version (6220)
Display of the actual software version.
9.2.18 LPB system
Device address (6600) andSegment address (6601)
The two-part LPB address of the controller consists of the 2-digit segment
number and the 2-digit device number.
Bus power supply function (6604)
Off: The controller does not provide the bus power supply.
Automatically: The bus power supply is switched on and off by the con
troller in accordance with the power demand of the bus system.
Bus power supply state (6605)
Off: The bus system power supply by the controller is currently inactive.
On: The bus system power supply by the controller is currently active.
Display system messages (6610)
This setting allows system messages which are transmitted via LPB to be
suppressed on connected operating elements.
Alarm delay (6612)
The transmission of the alarm to the BM module can be delayed in the ba
sic device by an adjustable time. This allows the prevention of unnecessa
ry messages to a service location caused by malfunctions which only oc
cur briefly (e.g. temperature monitor queried, communication errors). How
ever, it must be noted that malfunctions which occur briefly and quickly re-
occur are also filtered out by this.
Action changeover functions (6620)
If the setting Central is activated under prog. no. 6221 and 6223 respec
tively, the action for this setting can be set. The following settings are pos
sible:
Segment: The changeover is done for all controllers in the same seg
ment.
System: The changeover is done for all controllers in the entire system
(that is in all segments). The controller must be located in segment 0!
Summer changeover (6621)
Locally: The local heating circuit is switched on and off depending on
prog.no. 730, 1030 or 1330.
Locally: Depending on the settings made in prog. no. 6620, either the
heating circuits in this section or all heating circuits in the entire system
are switched on and off.
Optg mode changeover (6623)
Locally: The local heating circuit is switched on and off.
Centrally: Depending on the settings made in prog. no. 6620, either the
heating circuits in this section or all heating circuits in the entire system
are switched on and off.
Manual source lock (6624)
Locally: The local generator is locked.
Segment: All generators in the cascade are locked.
Hot water assignment (6625)
This setting is only necessary if the DHW heating control is provided by
the heating circuit time program (see prog. no. 1620 and 5061).
Local CHs: DHW heating applies only to the local heating circuit.
9 Settings
116
7636047 - 02 - 24082015
Содержание eurocondense four 125 kw
Страница 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Страница 39: ...5 5 2 Legend Fig 21 Legend for application examples part 1 5 Before installation 7636047 02 24082015 39 ...
Страница 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Страница 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Страница 146: ...Index 146 7636047 02 24082015 ...
Страница 148: ...7636047 02 24082015 ...