Boiler
Prog. no.
Level Standard value
Temp differential max
2316
C
- - -
Temp differential nominal
2317
C
15 °C
Pump modulation
None | Demand | Boiler setpoint | Temp differential nominal | Burner output
2320
E
Temp differential
nominal
Pump speed min
2322
E
10 %
Pump speed max
2323
E
100%
Output nominal
2330
E
EC four 125 kW: 125
kW
EC four 170 kW: 170
kW
EC four 215 kW: 215
kW
EC four 260 kW: 260
kW
EC four 300 kW: 300
kW
Output basic stage
2331
E
EC four 125 kW: 20
kW
EC four 170 kW: 28
kW
EC four 215 kW: 35
kW
EC four 260 kW: 42
kW
EC four 300 kW: 48
kW
Output at pump speed min
2334
E
10 %
Output at pump speed max
2335
E
90 %
Fan output heating max
(1)
2441
E
EC four 125 kW: 125
kW
EC four 170 kW: 170
kW
EC four 215 kW: 215
kW
EC four 260 kW: 260
kW
EC four 300 kW: 300
kW
Fan output full charging max
(1)
2442
E
EC four 125 kW: 125
kW
EC four 170 kW: 170
kW
EC four 215 kW: 215
kW
EC four 260 kW: 260
kW
EC four 300 kW: 300
kW
Fan output DHW max
(1)
2444
E
EC four 125 kW: 125
kW
EC four 170 kW: 170
kW
EC four 215 kW: 215
kW
EC four 260 kW: 260
kW
EC four 300 kW: 300
kW
Controller delay
Off | Heating mode only | Hot water mode only | Heating and HW mode
2450
E
Heating mode only
9 Settings
66
7636047 - 02 - 24082015
Содержание eurocondense four 125 kw
Страница 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Страница 39: ...5 5 2 Legend Fig 21 Legend for application examples part 1 5 Before installation 7636047 02 24082015 39 ...
Страница 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Страница 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Страница 146: ...Index 146 7636047 02 24082015 ...
Страница 148: ...7636047 02 24082015 ...