![Potterton eurocondense four 125 kw Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/potterton/eurocondense-four-125-kw/eurocondense-four-125-kw_installation-operation-and-maintanance-manual_1583026015.webp)
Model
EC four
125 kW
EC four
170 kW
EC four
215 kW
EC four
260 kW
EC four
300 kW
∆T = 10 K
mbar
109
132
146
154
156
Sound pressure level 1 m away
room air-dependent
dB(A)
40-51
40-51
40-52
40-53
40-54
room air-independent
dB(A)
39-50
39-50
39-51
40-52
40-53
Boiler weight
kg
205
240
285
314
344
Boiler water content
l
29
34
38
45
53
Height above everything
mm
1455
Width
mm
692
Depth
mm
1008
1171
1264
1357
3.2.3 Tables of sensor values
Tab.3
Resistance values for outside temperature sensor ATF
Temperature [°C]
Resistance [Ω]
-20
8194
-15
6256
-10
4825
-5
3758
0
2954
5
2342
10
1872
15
1508
20
1224
25
1000
30
823
Tab.4
Resistance values for all other sensors
Temperature [°C]
Resistance [Ω]
0
32555
5
25339
10
19873
15
15699
20
12488
25
10000
30
8059
35
6535
40
5330
45
4372
50
3605
55
2989
60
2490
65
2084
70
1753
75
1481
3 Technical specifications
7636047 - 02 - 24082015
15
Содержание eurocondense four 125 kw
Страница 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Страница 39: ...5 5 2 Legend Fig 21 Legend for application examples part 1 5 Before installation 7636047 02 24082015 39 ...
Страница 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Страница 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Страница 146: ...Index 146 7636047 02 24082015 ...
Страница 148: ...7636047 02 24082015 ...