Start of holiday (642 - 662)
Entering the holiday start.
End of holiday (643 - 663)
Entering the holiday end.
Operating level (648-668)
Selecting the operating level (Reduced or Off) for the holiday program.
Note
A holiday period always ends on the last day at 12:00 AM (00:00).
The holiday programmes are only activated in the operation
modeAutomatically .
9.2.6 Heating circuits
Comfort setpoint (710, 1010, 1310)
Setting of the comfort setpoint in the heating phases. Without room sensor
or with the room influence switched off (prog.no. 750, 1050, 1350), this
value is used for calculation of the flow temperature, to theoretically reach
the set room temperature.
Reduced temp setpoint (712, 1012, 1312)
Setting of the desired room temperature during the reduced heating
phase. Without room sensor or with the room influence switched off
(prog.no. 750, 1050, 1350), this value is used for calculation of the flow
temperature, to theoretically reach the set room temperature.
Frost protection setpoint (714, 1014, 1314)
Setting of the required room temperature during frost protection mode.
Without room sensor or with the room influence switched off (prog.no. 750,
1050, 1350), this value is used for calculation of the flow temperature, to
theoretically reach the set room temperature. The heating circuit remains
turned off until the flow temperature drops so far that the room tempera
ture falls below the frost protection temperature.
Heating curve slope (720, 1020, 1320)
Using the heating curve, the flow temperature setpoint is formed that is
used to regulate the heating circuit, subject to the outside temperature.
The gradient indicates how much the flow temperature changes by with
changing outside temperature.
9 Settings
86
7636047 - 02 - 24082015
Содержание eurocondense four 125 kw
Страница 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Страница 39: ...5 5 2 Legend Fig 21 Legend for application examples part 1 5 Before installation 7636047 02 24082015 39 ...
Страница 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Страница 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Страница 146: ...Index 146 7636047 02 24082015 ...
Страница 148: ...7636047 02 24082015 ...