Customer Services (858) 578-7887 & (888) GO IN
TEC
IN
TEC
Controls, 12700 Stowe Dr., Suite 1
0
0, Poway, CA 92064
Fax (858) 578-4633 & (888) FX IN
TEC
www.inteccontrols.com
Specification subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR
MGC2-20
PolyGard
®
Multi-Point Controller
User Manual - MGC2-20
Page 21
3.7.2 Software Version
Symbol Description
Default
Status Function
GC02-
XX
Software
Version
XX = Software Version
3.7.3 Maintenance Concept
The MGC2 system monitors the maintenance intervals as required, by local Regulations or Customer
requirements.
During startup and/or after maintenance the date for next maintenance is entered. When this date is reached at 9
o'clock the next morning a failure signal is activated and Start Menu displays the phone No. of the service
company. The failure signal (maintenance) can be acknowledged by the operator. The maintenance message
(Service Phone No.) is reset after maintenance is accomplished and a new maintenance date is entered.
The service phone number can be individually entered in the next menu.
Symbol
Description
Default
Status Function
MM.DD.YY Maintenance
MM.DD.YY = Input date for next maintenance.
8585....
Phone No.
Input the individual service phone No.
3.7.4 Average Value Function
The Controller calculates for each active sensing point the arithmetic average value from 10 measurements within
the time unit defined in this menu “AV-time”. This average value is indicated in the menu “Sensor Readings” near
the Current Value. During each Sensor Point Setup the control mode of Current Value or Average Value for the
Stage/Setpoint evaluation is defined.
The evaluation of the control mode Average Value is overlaid by the Current Value, if this exceeds Stage/Setpoint
defined in the menu “AV-Overlay”. The overlay is delayed by the time factor set in this menu.
Symbol Description Default
Status
Function
120 s
120pm
AV- Overlay 120 s
120 ppm
sec. = Delay time average value Overlay. 0 = No overlay Function
ppm = Threshold average Overlay
1800 s
AV-Time
1800 s
sec. = Time to calculate average value
3.7.5 Time, Date
Input and correction of the system time and date. Selection of the time and date format.
Symbol
Description Default
Status
Function
US
Time format US
EU = Display time and date in EU format
US = Display time and date in US format
hh.mm.ss Time
hh.mm.ss = Input the correct time (EU format)
hh.mm.ss am = Input the correct time (US format)
MM.DD.YY Date
TT.MM.JJ = Input the correct date (EU format)
MM.DD.YY = Input the correct date (US format)