MGC2-20
PolyGard
®
Multi-Point Controller
User Manual - MGC2-20
Page 10
SP 01 NH3 ppm
50 *AV 33 CV
3.3.1 Manual operation of the relays
The manual operation of the relays can be accomplished in the menu “Relay Status”. If a relay is in the Manual ON
or Manual OFF status, the yellow LED at the Controller is on continuously.
The external operation of a relay by an assigned digital input has priority before the manual operation or the Stage
set point of a sensor point being exceeded.
Manually operated relays can be reset by selecting the “Automatic” mode.
The reset of Latching relays also is a function in this menu.
Select Relay
Select Function Manual operation
Manual ON = Relay ON
Select Function
Manual OFF = Relay OFF
Automatic
= Automatic operation restored
Reset ?
= Reset of latched relay
Relay forced to OFF Condition
3.4 Menu Sensor Readings
In this menu it displays the current value (CV) and average value (AV) with sensor unit and type for each active
sensor point (SP) as well as the defined mode of control (CV or AV mode) with “*” .
Symbol Description
Setting
Status
Function
SP 01
Sensor Point
No.
Select SP No.
NH3
Type
NH3
See 3.6.2
ppm
Unit
See 3.6.2
CV
Current value CV
Current value of Gas Concentration
AV
Average value
Average value (10 measured values within the time unit)
*
Control mode
Display for the Control mode selected. (CV or AV)
Not active SP Status
Not active SP disabled
Error
SP Malfunction
Current signal < 3 mA or > 22 mA
R 01
OFF
Manual ON
Manual OFF
Manual OFF