MGC2-20
PolyGard
®
Multi-Point Controller
User Manual - MGC2-20
Page 11
3.5 Menu Relay Setup
Display and change the parameters for each relay.
(Main menu)
(Selection Relay No.)
Relay Mode
See 3.5.1
Relay Function
See 3.5.2
Activate Latching Mode
See 3.5.3
Definition of Horn Functions
See 3.5.4
Definition of external Relay Operation
See 3.5.5
Set Delay ON time
See 3.5.6
Set Delay OFF time
See 3.5.6
3.5.1 Relay Mode
Symbol Description
Setting
Status
Function
R 01
Relay No.
Selection Relay
De-
energized Relay Mode
De-
energized
De-energized
Energized
= Stage ON = Relay ON
= Stage ON = Relay OFF
3.5.2 Relay Action Steady / Flash
Symbol Description
Setting
Status
Function
R 01
Relay No.
Selection Relay
0
Function
0
0 = Relay Function steady
> 0 = Relay Function flashing (= Periods time sec.)
Impulse / Break = 1:1
Relay Mode
De- energized
Steady / Flash
0 s
Relay Setup
R 01
Latching mode
No
Time Reset DI
0s 0
0
External mode
DI: ON = 0: OFF = 0
Delay ON time
0 s
Delay OFF time
0 s