Customer Services (858) 578-7887 & (888) GO IN
TEC
IN
TEC
Controls, 12700 Stowe Dr., Suite 1
0
0, Poway, CA 92064
Fax (858) 578-4633 & (888) FX IN
TEC
www.inteccontrols.com
Specification subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR
MGC2-20
PolyGard
®
Multi-Point Controller
User Manual - MGC2-20
Page 34
7 Specifications MGC2-20
Electrical
Power supply
120 VAC (90 to 230 VAC) 50/60Hz
resettable breaker
Power Consumption
60 VA, max.
RF/RMI proteced
4.0 W @ 3 ft. (1 m) radiated
Type of control
General
Five-stage (S1 to S5) control, assignable up to
twenty (20) binary/relay output, i.e.
Low-med-high-fault / fail-horn*, or low1-low 2-
med1-med2-high, or any other combinations
(* = horn/audible alarm built-in and factory pre-
configured to relay output “R20”)
Analog Input
Twenty (20), 4 - 20 mA
Analog reading
Current and mean (average) value
Power supply for Analog inputs
24 VDC max. 50 mA / channel
Stage level / setpoint
Field adjustable over full range, five (5) per
analog input, assignable to current or mean
(average) value
- hysteresis/ switching differential
Selectable for each sensor point
Digital inputs
Four (4) each can be individually assigned to
any relay (R1..R20). Digital inputs are used for
remote audio/visual alarm reset
Relay outputs (R1-R20) w/ status LEDs
Twenty (20) SPDT, 8 A, 24 VAC/VDC -250
VAC contact resistance 100 m
, max.
- each stage level (S1-S5)
Assignable to any relay
- sensor fail-safe
Assignable to any stage level
Time delay switching
Selectable for make and brake of each sensor
point (SP1 to SP20) 0-9,999 seconds
VDC output supply
24 VDC, 0.5 A fused
Analog output
Ten (10) independent 4 - 20 mA signal, 500
max. load, selectable as low, high or averaging
of sensor inputs
Audible alarm
90 db, enabled or disabled, selectable;
assignable to stage level S1, S2, S3, S4 or S5
Alarm acknowledgement
Menu-driven and system reset function for
latched relays
User Interface
Keypad type
See 2.1 “Description Keypad User Interface”
Touch buttons
Six (6)
Status LED’s
Yellow: Alarm; Red: Fault (fail)
Digital display
Liquid Crystal Display (LCD), two lines, 16
characters per line, 1 digit resolution, backlit
- unit display
Menu selectable, per sensor;
ppm, %v/v, %LEL; °F or % RH
Environmental
Permissible ambient
- working temperature
23 °F to 104 °F (-5 °C to+ 40 °C)
- storage temperature
-4 °F to 104 °F (-20 °C to + 40 °C)
- humidity
15 to 95 % RH non condensing
- working pressure
Atmospheric ± 10%