circulating  pump  is  used,  it  is  important  to  note  that  the  flow  rate 

should be slow so that there will be a minimum of turbulence inside 

the water heater storage tank.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 

circulating line on the outlet side of the pump. Never throttle flow 

on the suction side of a pump. See Figure 55 in Piping Diagrams.

NOTE:

  In  addition  to  the  factory  installed  Temperature-Pressure 

Relief Valve (T&P valve) on the water heater, each remote storage 

tank that may be installed and piped to a water heating appliance must 

also have its own properly sized, rated and approved Temperature-

Pressure  Relief  Valve  installed.  See  Temperature-Pressure  Relief 

Valve on Page 20. 

Call the toll free technical support phone number listed on the back 

cover of this manual for further assistance in sizing a T&P valve for 

remote storage tanks.

THERMOMETERS (NOT SUPPLIED)

Thermometers are installed in the water piping system as a means 

of detecting the temperature of the hot water supply at critical points 

in the system. Field supplied thermometers should be obtained and 

installed. See Piping Diagrams beginning on Page 59.

WATER (POTABLE) HEATING AND SPACE HEATING

1. 

All water piping components connected to the water heater that 

are for space heating applications shall be suitable for use with 

potable water.

2. 

Toxic chemicals, such as those used for boiler treatment, must 

NEVER be introduced into this system.

3. 

The  water  heaters  covered  in  this  manual  may  never  be 

connected  to  any  existing  heating  system  or  component(s) 

previously used with non-potable water heating appliance.

4. 

When the system requires water for space heating that exceed 

safe temperatures at domestic water fixtures a mixing valve must 

be installed, see Mixing Valves on Page 18.

5. 

These  water  heaters  cannot  be  used  in  space  heating 

applications only.

HOTTER WATER CAN SCALD: 

Water heaters are intended to produce hot water. Water heated to 

a  temperature  which  will  satisfy  space  heating,  clothes  washing, 

dish washing, cleaning and other sanitizing needs can scald and 

permanently injure you upon contact. Some people are more likely 

to be permanently injured by hot water than others. These include 

the elderly, children, the physically or developmentally disabled. If 

anyone using hot water fits into one of these groups or if there is a 

local code or state law requiring a certain temperature water at the 

hot water tap, then you must take special precautions. In addition 

to using the lowest possible temperature setting that satisfies your 

hot water needs, a means such as a mixing valve should be used 

at the hot water taps used by these people or at the water heater. 

See  Figure  8  in  Mixing  Valves.  Valves  for  reducing  point  of  use 

temperature by mixing cold and hot water are also available:

Consult  a  Qualified  Installer  or  Service  Agency.  Follow 

manufacturer’s  instructions  for  installation  of  the  valves.  Before 

changing the factory setting on the thermostat, read the Temperature 

Regulation section beginning on Page 35.

T&P VALVE DISCHARGE PIPE

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

This water heater is provided with a properly rated/sized and 

certified  combination  temperature  -  pressure  (T&P)  relief 

valve by the manufacturer. See Temperature-Pressure Relief 

Valve on page 20 for information on replacement and other 

requirements.

Water Damage Hazard

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

CAUTION

Install a discharge pipe between the T&P valve discharge opening 

and a suitable floor drain. Do not connect discharge piping directly 

to the drain unless a 6” (15.2 cm) air gap is provided. To prevent 

bodily injury, hazard to life, or property damage, the Temperature-

Pressure  Relief  Valve  must  be  allowed  to  discharge  water  in 

adequate quantities should circumstances demand. If the discharge 

pipe is not connected to a drain or other suitable means, the water 

flow may cause property damage.

T&P VALVE DISCHARGE PIPE REQUIREMENTS:

•  Shall not be smaller in size than the outlet pipe size of the 

valve, or have any reducing couplings or other restrictions.

• 

Shall not be plugged or blocked.

• 

Shall not be exposed to freezing temperatures.

• 

Shall be of material listed for hot water distribution.

• 

Shall be installed so as to allow complete drainage of both the 

Temperature-Pressure Relief Valve and the discharge pipe.

• 

Must terminate a maximum of six inches above a floor 

drain or external to the building. In cold climates, it is 

recommended that the discharge pipe be terminated at an 

adequate drain inside the building.

• 

Shall not have any valve or other obstruction between the 

Temperature-Pressure Relief Valve and the drain.

Содержание BSS

Страница 1: ...tly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WH...

Страница 2: ...take Moisture Protection 25 Horizontal Vent Terminal Installation 25 Vertical Vent Terminal Installation 26 Termination Clearances Sidewall Direct Vent 27 Direct Vent Installation Diagrams 28 Concentr...

Страница 3: ...ot follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in injury or death T...

Страница 4: ...Explosion Hazard Overheated water can cause water tank explosion Properly sized Temperature Pressure Relief Valve must be installed in the opening provided Verify the power to the water heater is tur...

Страница 5: ...5 GENERAL SAFETY INFORMATION...

Страница 6: ...nderstand instruction manual Breathing Hazard Carbon Monoxide Gas Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION Fire and Explosion Hazard Le...

Страница 7: ...tally vented gas fueled heating appliance or equipment The sign should read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Страница 8: ...These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed as shown Particular attention should be given to th...

Страница 9: ...8 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 cm 123 19 55 88 40 102 87 104 14 16 19 13 97 16 82 50 130 Inches 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5 8 cm 165 7 55 88 40 138 43 139 7 16 19 13 97 16...

Страница 10: ...pressure must be maintained under both load and no load dynamic and static conditions Table 3 RECOVERY CAPACITIES Input Recovery Capacities Rating Btu hr Rating kW Temp Rise F 30 40 50 60 70 80 90 100...

Страница 11: ...at the bottom of heater behind the Access Doors 1 30 11 15 2 3 23 34 33 CAUTION HARNESS HAS 120 VAC IN OPERATION See Venting Installation and Condensate Piping for more information Figure 2 34 GALLON...

Страница 12: ...ation 50 GALLON UNIT FEATURES AND COMPONENTS CONT Figure 3 50 GALLON UNIT This is a view of the area at the bottom of heater behind the Access Doors 1 2 3 15 32 27 33 29 32 24 26 20 19 12 11 25 13 28...

Страница 13: ...ndensate Drain Outlet 13 Enable Disable Switch 14 Hot Water Outlet 15 Gas Supply 16 Main Manual Gas Shutoff Valve 17 Union 18 Inlet Water Shutoff Valve 19 Cold Water Inlet 20 T P Relief Valve 21 Ratin...

Страница 14: ...pressure switch that requires an increase in negative pressure to change the electrical contacts from normally closed to open The switch is connected to the pressure tap on the PVC pipe connected to...

Страница 15: ...ater heater close to a 120 VAC power supply See Power Supply on Page 18 for requirements 8 Locate the water heater where an adequate supply of fresh air for combustion and ventilation can be obtained...

Страница 16: ...ter heater Do not cover the outer door thermostat or temperature pressure relief valve Do not cover the instruction manual Keep it on the side of the water heater or nearby for future reference Doobta...

Страница 17: ...d at or above the input Btu hr rating of the water heater they supply 2 Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heate...

Страница 18: ...4 Water Temperature F C Time for 1st Degree Burn Less Severe Burns Time for Permanent Burns 2nd 3rd Degree Most Severe Burns 110 43 3 normal shower temp 116 46 7 pain threshold 116 46 7 35 minutes 45...

Страница 19: ...ed in the cold water supply line an expansion tank must be installed between the check valve and the water heater s cold water inlet Set storage tank temperature five degrees lower than the water heat...

Страница 20: ...ature Pressure Relief Valve on the water heater each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized rated and approved Temperatu...

Страница 21: ...the building In cold climates it is recommended that the discharge pipe be terminated at an adequate drain inside the building Shall not have any valve or other obstruction between the temperature pr...

Страница 22: ...bustion air intake and the exhaust vent terminal Refer to Horizontal Vent Terminal Installation on Page 25 and Vertical Vent Terminal Installation on Page 26 GENERAL VENTING INSTRUCTIONS The following...

Страница 23: ...e personal injury death or substantial property damage Installations must comply with applicable national state and local codes For Canadian installation Polypropylene vent must be listed as a ULC S63...

Страница 24: ...000 ft 610 m to 7 700 ft 2 347 m IMPORTANT Do not use vent elbows in this vent pipe installation See Figure 12 90 Short Sweep Elbow 90 Long Sweep Elbow 45 Sweep Elbow Correct Fittings Incorrect Fittin...

Страница 25: ...hat it vents through the roof please refer to Vertical Vent Terminal Installation on Page 26 1 A f t e r t h e p o i n t s o f t e r m i n a t i o n h a v e b e e n determined see Vent Pipe Terminatio...

Страница 26: ...nings above anticipated snow levels FLAT ROOF INSTALLATION On flat roof installations the air intake and the exhaust vent terminations must be a minimum of 24 inches 60 cm above any parapet vertical w...

Страница 27: ...ir supply inlet into building or combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm f...

Страница 28: ...uations See the section on Direct Vent Air Intake Moisture Protection on page 25 Figure 24 SIDEWALL VENT INSTALLATION ALL MODELS See Note 3 See Note 3 Drain Pan Piped To Adequate Drain See Note 1 See...

Страница 29: ...t of a qualified installer or qualified service technician see Page 8 All precautions in the literature on tags and labels attached to the unit must be observed Follow all safety codes Wear safety gla...

Страница 30: ...ARIS UNITS 175 000 199 000 BTU HR MODELS When using two water heaters with inputs of 175 000 BTH HR or above install vent terminations using either Method A or Method B below Figure 33 When using thre...

Страница 31: ...pany will have to install a properly sized gas meter Make sure the gas supplied is the same type listed on the water heaters rating label The gas piping must be installed according to all local and st...

Страница 32: ...y of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases at 11 inches water column pressure Based on a Pressure Drop of 0 5 Inch Water Column Additional tables are available in th...

Страница 33: ...ay coil to this circuit This will damage the CCB circuit board and is not covered under the limited warranty CONNECTING AN EXTERNAL SUPERVISORY CONTROL The enable disable circuit is accessed from the...

Страница 34: ...or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot wat...

Страница 35: ...120 F Status Heating MENU HELP GAS OFF O N Figure 38 HIGH TEMPERATURE LIMIT CONTROL ECO This water heater is equipped with an ECO energy cut out non adjustable high temperature limit switch The ECO i...

Страница 36: ...ion of the various operational states The Desktop screen also displays animated Status Icons to convey operational information see Table 12 on Page 37 for descriptions of the Status Icons OVERVIEW The...

Страница 37: ...control system or when the Enable Disable switch located at the base of the water heater is in disable position The Combustion Blower is being energized The Spark Igniter is being energized See Spark...

Страница 38: ...ot reset the control system if the condition that caused the Fault has not been corrected Heating Disabled The heating is disabled by the Enable Disable switch located at the base of the water heater...

Страница 39: ...will be displayed Tank Temperature 71 F Operating Setpoint 120 F Status Standby HELP MANUFACTURER MODEL INFORMATION MENU The Main Menu is where all control system menus are listed see Table 14 on page...

Страница 40: ...fferential Adjustment on page 39 Temperatures HELP BACK Operating Setpoint 120 F Differential 8 F Tank Temperature 120 F Tank Probe Offset 0 F HEATER STATUS MENU DESCRIPTION ACTION DISPLAY Press Heate...

Страница 41: ...ersion Software version for user interface module Use External Enable Enables Disables the external enable circuit External Enable Status Displays whether or not the external enable circuit has been a...

Страница 42: ...last nine 9 Fault andAlert messages with a time stamp The newest event will replace the oldest Press the Fault to view details for each Fault or Alert message stored Fault History HELP BACK 1 Upper T...

Страница 43: ...to Yes and press ACCEPT to save the new setting NOTE The Access Code at the bottom of the Service Contact Information screen is for manufacturing engineering purposes only There are no user settings...

Страница 44: ...Sequence of Operation See the Sequence of Operation Flow Chart on page 49 Ensure the water heater is properly grounded Flame sensing requires an adequate earth ground If the water heater is not proper...

Страница 45: ...42 On the water heaters covered by this manual there are test ports for supply and manifold gas pressure readings on the gas control valve Using a small flat tip pocket screw driver open the needle v...

Страница 46: ...t a t s o m r e h t e h t t e S o t s e t u n i m 5 e v i f t i a W s a g y n a t u o r a e l c s a g l l e m s n e h t u o y f I n i B w o l l o F P O T S u o y f I l e b a l s i h t n o e v o b a n...

Страница 47: ...The display CCB and other electrical components will still be energized and the display will read Water Heating Disabled 3 Close Main Gas Shutoff Valve see Figure 37 on page 31 GAS INPUT RATE The gas...

Страница 48: ...represents some of the most critical installation requirements that when overlooked often result in operational problems down time and needless parts replacement This is not a complete list Before pe...

Страница 49: ...setting a heating cycle is activated Igniter is energized 24 V Gas Control Valve is energized gas flows to Main Burner 24 V Gas Control Valve de energized 24 V Gas Control Valve de energized Is flame...

Страница 50: ...e to have the complete water heater Model Number Serial Number and Series Number available This information can be found on the rating plate affixed to the water heater For more information or technic...

Страница 51: ...l continue to lock out DIAGNOSTIC CHECKS Turn off power to the water heater before performing any service Electrical Shock Hazard Label all wires prior to disconnecting when performing service Wiring...

Страница 52: ...continuity when the blower is off and closed shorted when the blower is on Replace the switch if necessary ADVANCED BACK 0 days 0 hrs 0 mins ago Error Code A7 1201 Blocked Air Intake Restriction in ai...

Страница 53: ...the valve being slightly opened Not shown in Figure 46 F The drain valve may be leaking at the tank fitting Not shown in Figure 46 G Leakage from recirculation plug or pipe connection Not shown in Fig...

Страница 54: ...n the hose clamp at the adaptor rubber boot and slide the plastic pipe out and away from the adaptor rubber boot See Figure 14 in Integrated Filter Installation Remove the adaptor rubber boot containi...

Страница 55: ...ter heater drain valve and terminate it to an adequate drain 7 Open the water heater drain valve and allow all the water to drain from the storage tank 8 Close the water heater drain valve when all wa...

Страница 56: ...CONTROL BOARD LAYOUT 11 12 1 J16 J5 J3 J13 J4 J17 J10 J9 J14 J15 J1 J6 J12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 6 6 6 7 7 8 8...

Страница 57: ...iolet CCB J3 5V Data Data D gnd SDA data SCL data Write protect 5V Dgnd CCB J12 2 Red 3 Green 4 White Brown 5 White Blue 6 White Orange Key Gas Valve L1 Neutral Protective Earth MAIN INPUT 3 CIRCUIT B...

Страница 58: ...POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION Figure 50 CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TE...

Страница 59: ...s Mixing Valve Metal Drain Pan 6 15 2cm Air Gap Max Adequate Drain set to 120 F 48 8 C or lower Mixing Valve Figure 52 TYPICAL ONE TEMPERATURE SYSTEM PIPING INSTALLATION All Models Figure 53 SAMPLE MI...

Страница 60: ...ixing Valve Manual Shut Off Valve Typ Mixing Valve 180 F Max Figure 54 AIR HANDLER PIPING INSTALLATION All Models Figure 55 POLARIS WITH AUXILLARY STORAGE TANK One or Two Temperature System With or Wi...

Страница 61: ...61 NOTES...

Страница 62: ...62 NOTES...

Страница 63: ...For Tech Support please call PGC models 1 800 456 9805 SPC models 1 800 365 0024 BSS BTS models 1 800 527 1953 Copyright 2016 A O Smith Corporation All rights reserved...

Отзывы: