Polaris BSS Скачать руководство пользователя страница 31

31

WATER HEATER INSTALLATION 

CONDENSATE DRAIN INSTALLATION

1. 

Ensure the water heater’s enable/disable switch is in the “disable” 

position.

2. 

Install a 1/2 inch PVC condensate drain line between condensate 

drain  connection  on  the  Exhaust/Condensate  Elbow  and  a 

suitable building drain with a slight downward slope to drain. The 

exhaust elbow has a “built in” condensate trap. Do not install an 

additional trap in the condensate drain piping. See Figure 36.

3. 

Terminate the condensate drain piping with an elbow above the 

drain. Ensure that any discharge will exit the condensate drain 

line no more than 6 inches (15.2 cm) above a suitable building 

drain, or external to the building, see Figure 36.

NOTE:

 In cold climates it is recommended the condensate drain be 

terminated at a suitable drain inside the building.

4. 

Ensure  the  condensate  drain  line  is  not  elevated  above  the 

condensate drain connection on the Exhaust/Condensate Elbow, 

see Figure 36.

5. 

Brace  the  condensate  drain  line  with  floor  mounted  standoffs 

every three feet.

6. 

Ensure  the  condensate  drains  freely  during  start  up  and  the 

condensate clean out cap is on and tight when unit is in operation.

7. 

Condensate clean out cap must be on and tight when unit is in 

operation.

DRAIN LINE TO

TERMINATE NO

MORE THAN 6

INCHES (15.2 cm)

ABOVE DRAIN

BUILDING

DRAIN

1/2” NPT

CONDENSATE

DRAIN

CONNECTION

CONDENSATE

CLEANOUT

EXHAUST/CONDENSATE

(VENT) ELBOW

PRESSURE PORT

CONDENSATE DRAIN

LINE - FIELD 

INSTALLED

Figure 36

SUPPLY GAS LINE INSTALLATION

Contact your local gas utility company to ensure that adequate gas 

service  is  available  and  to  review  applicable  installation  codes  for 

your area.

Be  sure  that  the  gas  meter  has  sufficient  capacity  to  supply  the 

rated gas input of the water heater as well as the requirements of 

all other gas fired equipment supplied by the meter. If the gas meter 

is undersized, the gas company will have to install a properly sized 

gas meter.

Make  sure  the  gas  supplied  is  the  same  type  listed  on  the  water 

heaters rating label.

The  gas  piping  must  be  installed  according  to  all  local  and  state 

codes  or  in  absence  of  local  and  state  codes  with  the  “National 

Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current edition. Canadian 

installations  must  be  performed  in  accordance  with  CAN/CSA-

B149.1-current edition.
Schedule  40  Steel  or  Wrought  Iron  Pipe  is  the  preferred  material 

for  the  gas  line  of  this  water  heater.  It  is  imperative  to  follow  the 

sizing  recommendations  in  the  latest  version  of  the  National  Fuel 

Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as 

the gas line for this water heater.
Tables 8, 9, and 10 on Page 32 are provided as a sizing reference for 

commonly used gas pipe materials. Consult the “National Fuel Gas 

Code” for the recommended gas pipe size of other materials.
Follow  the  instructions  below  and  reference  Figure  37  for  gas 

piping installation.
1. 

Apply  thread  sealing  compounds  (pipe  dope/  Teflon  tape) 

sparingly and only to the male threads of the pipe joints. Do 

not apply sealing compound to the first two threads. Use pipe 

dope or Teflon tape marked as being resistant to the action of 

liquid petroleum (LP/propane) gases.

2. 

Install a readily accessible manual shut-off valve in the gas 

supply  line  as  recommended  by  the  local  utility.  Know  the 

location of this valve and how to turn off the gas to this unit.

3. 

Install a sediment trap as shown. The sediment trap must be 

no less than 3 inches long for the accumulation of dirt, foreign 

material and water droplets.

4. 

Install  a  ground  union  between  the  water  heater  and  the 

manual  shut-off  valve.  This  is  to  allow  easy  servicing.  See 

Figure 37 below.

5. 

Turn the gas supply on and check for leaks. See Gas Line 

Leak  Testing  on  Page  32.  Use  a  chloride-free  soap  and 

water  solution  (bubbles  forming  indicate  a  leak)  or  other 

approved method.

NOTE:

 Units with inputs of 175,000 BTU/HR or above must have a 

minimum of 3/4” NPT gas pipe supplied to the water heater.

Sediment Trap

Figure 37

Содержание BSS

Страница 1: ...tly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WH...

Страница 2: ...take Moisture Protection 25 Horizontal Vent Terminal Installation 25 Vertical Vent Terminal Installation 26 Termination Clearances Sidewall Direct Vent 27 Direct Vent Installation Diagrams 28 Concentr...

Страница 3: ...ot follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in injury or death T...

Страница 4: ...Explosion Hazard Overheated water can cause water tank explosion Properly sized Temperature Pressure Relief Valve must be installed in the opening provided Verify the power to the water heater is tur...

Страница 5: ...5 GENERAL SAFETY INFORMATION...

Страница 6: ...nderstand instruction manual Breathing Hazard Carbon Monoxide Gas Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION Fire and Explosion Hazard Le...

Страница 7: ...tally vented gas fueled heating appliance or equipment The sign should read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Страница 8: ...These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed as shown Particular attention should be given to th...

Страница 9: ...8 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 cm 123 19 55 88 40 102 87 104 14 16 19 13 97 16 82 50 130 Inches 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5 8 cm 165 7 55 88 40 138 43 139 7 16 19 13 97 16...

Страница 10: ...pressure must be maintained under both load and no load dynamic and static conditions Table 3 RECOVERY CAPACITIES Input Recovery Capacities Rating Btu hr Rating kW Temp Rise F 30 40 50 60 70 80 90 100...

Страница 11: ...at the bottom of heater behind the Access Doors 1 30 11 15 2 3 23 34 33 CAUTION HARNESS HAS 120 VAC IN OPERATION See Venting Installation and Condensate Piping for more information Figure 2 34 GALLON...

Страница 12: ...ation 50 GALLON UNIT FEATURES AND COMPONENTS CONT Figure 3 50 GALLON UNIT This is a view of the area at the bottom of heater behind the Access Doors 1 2 3 15 32 27 33 29 32 24 26 20 19 12 11 25 13 28...

Страница 13: ...ndensate Drain Outlet 13 Enable Disable Switch 14 Hot Water Outlet 15 Gas Supply 16 Main Manual Gas Shutoff Valve 17 Union 18 Inlet Water Shutoff Valve 19 Cold Water Inlet 20 T P Relief Valve 21 Ratin...

Страница 14: ...pressure switch that requires an increase in negative pressure to change the electrical contacts from normally closed to open The switch is connected to the pressure tap on the PVC pipe connected to...

Страница 15: ...ater heater close to a 120 VAC power supply See Power Supply on Page 18 for requirements 8 Locate the water heater where an adequate supply of fresh air for combustion and ventilation can be obtained...

Страница 16: ...ter heater Do not cover the outer door thermostat or temperature pressure relief valve Do not cover the instruction manual Keep it on the side of the water heater or nearby for future reference Doobta...

Страница 17: ...d at or above the input Btu hr rating of the water heater they supply 2 Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heate...

Страница 18: ...4 Water Temperature F C Time for 1st Degree Burn Less Severe Burns Time for Permanent Burns 2nd 3rd Degree Most Severe Burns 110 43 3 normal shower temp 116 46 7 pain threshold 116 46 7 35 minutes 45...

Страница 19: ...ed in the cold water supply line an expansion tank must be installed between the check valve and the water heater s cold water inlet Set storage tank temperature five degrees lower than the water heat...

Страница 20: ...ature Pressure Relief Valve on the water heater each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized rated and approved Temperatu...

Страница 21: ...the building In cold climates it is recommended that the discharge pipe be terminated at an adequate drain inside the building Shall not have any valve or other obstruction between the temperature pr...

Страница 22: ...bustion air intake and the exhaust vent terminal Refer to Horizontal Vent Terminal Installation on Page 25 and Vertical Vent Terminal Installation on Page 26 GENERAL VENTING INSTRUCTIONS The following...

Страница 23: ...e personal injury death or substantial property damage Installations must comply with applicable national state and local codes For Canadian installation Polypropylene vent must be listed as a ULC S63...

Страница 24: ...000 ft 610 m to 7 700 ft 2 347 m IMPORTANT Do not use vent elbows in this vent pipe installation See Figure 12 90 Short Sweep Elbow 90 Long Sweep Elbow 45 Sweep Elbow Correct Fittings Incorrect Fittin...

Страница 25: ...hat it vents through the roof please refer to Vertical Vent Terminal Installation on Page 26 1 A f t e r t h e p o i n t s o f t e r m i n a t i o n h a v e b e e n determined see Vent Pipe Terminatio...

Страница 26: ...nings above anticipated snow levels FLAT ROOF INSTALLATION On flat roof installations the air intake and the exhaust vent terminations must be a minimum of 24 inches 60 cm above any parapet vertical w...

Страница 27: ...ir supply inlet into building or combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm f...

Страница 28: ...uations See the section on Direct Vent Air Intake Moisture Protection on page 25 Figure 24 SIDEWALL VENT INSTALLATION ALL MODELS See Note 3 See Note 3 Drain Pan Piped To Adequate Drain See Note 1 See...

Страница 29: ...t of a qualified installer or qualified service technician see Page 8 All precautions in the literature on tags and labels attached to the unit must be observed Follow all safety codes Wear safety gla...

Страница 30: ...ARIS UNITS 175 000 199 000 BTU HR MODELS When using two water heaters with inputs of 175 000 BTH HR or above install vent terminations using either Method A or Method B below Figure 33 When using thre...

Страница 31: ...pany will have to install a properly sized gas meter Make sure the gas supplied is the same type listed on the water heaters rating label The gas piping must be installed according to all local and st...

Страница 32: ...y of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases at 11 inches water column pressure Based on a Pressure Drop of 0 5 Inch Water Column Additional tables are available in th...

Страница 33: ...ay coil to this circuit This will damage the CCB circuit board and is not covered under the limited warranty CONNECTING AN EXTERNAL SUPERVISORY CONTROL The enable disable circuit is accessed from the...

Страница 34: ...or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot wat...

Страница 35: ...120 F Status Heating MENU HELP GAS OFF O N Figure 38 HIGH TEMPERATURE LIMIT CONTROL ECO This water heater is equipped with an ECO energy cut out non adjustable high temperature limit switch The ECO i...

Страница 36: ...ion of the various operational states The Desktop screen also displays animated Status Icons to convey operational information see Table 12 on Page 37 for descriptions of the Status Icons OVERVIEW The...

Страница 37: ...control system or when the Enable Disable switch located at the base of the water heater is in disable position The Combustion Blower is being energized The Spark Igniter is being energized See Spark...

Страница 38: ...ot reset the control system if the condition that caused the Fault has not been corrected Heating Disabled The heating is disabled by the Enable Disable switch located at the base of the water heater...

Страница 39: ...will be displayed Tank Temperature 71 F Operating Setpoint 120 F Status Standby HELP MANUFACTURER MODEL INFORMATION MENU The Main Menu is where all control system menus are listed see Table 14 on page...

Страница 40: ...fferential Adjustment on page 39 Temperatures HELP BACK Operating Setpoint 120 F Differential 8 F Tank Temperature 120 F Tank Probe Offset 0 F HEATER STATUS MENU DESCRIPTION ACTION DISPLAY Press Heate...

Страница 41: ...ersion Software version for user interface module Use External Enable Enables Disables the external enable circuit External Enable Status Displays whether or not the external enable circuit has been a...

Страница 42: ...last nine 9 Fault andAlert messages with a time stamp The newest event will replace the oldest Press the Fault to view details for each Fault or Alert message stored Fault History HELP BACK 1 Upper T...

Страница 43: ...to Yes and press ACCEPT to save the new setting NOTE The Access Code at the bottom of the Service Contact Information screen is for manufacturing engineering purposes only There are no user settings...

Страница 44: ...Sequence of Operation See the Sequence of Operation Flow Chart on page 49 Ensure the water heater is properly grounded Flame sensing requires an adequate earth ground If the water heater is not proper...

Страница 45: ...42 On the water heaters covered by this manual there are test ports for supply and manifold gas pressure readings on the gas control valve Using a small flat tip pocket screw driver open the needle v...

Страница 46: ...t a t s o m r e h t e h t t e S o t s e t u n i m 5 e v i f t i a W s a g y n a t u o r a e l c s a g l l e m s n e h t u o y f I n i B w o l l o F P O T S u o y f I l e b a l s i h t n o e v o b a n...

Страница 47: ...The display CCB and other electrical components will still be energized and the display will read Water Heating Disabled 3 Close Main Gas Shutoff Valve see Figure 37 on page 31 GAS INPUT RATE The gas...

Страница 48: ...represents some of the most critical installation requirements that when overlooked often result in operational problems down time and needless parts replacement This is not a complete list Before pe...

Страница 49: ...setting a heating cycle is activated Igniter is energized 24 V Gas Control Valve is energized gas flows to Main Burner 24 V Gas Control Valve de energized 24 V Gas Control Valve de energized Is flame...

Страница 50: ...e to have the complete water heater Model Number Serial Number and Series Number available This information can be found on the rating plate affixed to the water heater For more information or technic...

Страница 51: ...l continue to lock out DIAGNOSTIC CHECKS Turn off power to the water heater before performing any service Electrical Shock Hazard Label all wires prior to disconnecting when performing service Wiring...

Страница 52: ...continuity when the blower is off and closed shorted when the blower is on Replace the switch if necessary ADVANCED BACK 0 days 0 hrs 0 mins ago Error Code A7 1201 Blocked Air Intake Restriction in ai...

Страница 53: ...the valve being slightly opened Not shown in Figure 46 F The drain valve may be leaking at the tank fitting Not shown in Figure 46 G Leakage from recirculation plug or pipe connection Not shown in Fig...

Страница 54: ...n the hose clamp at the adaptor rubber boot and slide the plastic pipe out and away from the adaptor rubber boot See Figure 14 in Integrated Filter Installation Remove the adaptor rubber boot containi...

Страница 55: ...ter heater drain valve and terminate it to an adequate drain 7 Open the water heater drain valve and allow all the water to drain from the storage tank 8 Close the water heater drain valve when all wa...

Страница 56: ...CONTROL BOARD LAYOUT 11 12 1 J16 J5 J3 J13 J4 J17 J10 J9 J14 J15 J1 J6 J12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 6 6 6 7 7 8 8...

Страница 57: ...iolet CCB J3 5V Data Data D gnd SDA data SCL data Write protect 5V Dgnd CCB J12 2 Red 3 Green 4 White Brown 5 White Blue 6 White Orange Key Gas Valve L1 Neutral Protective Earth MAIN INPUT 3 CIRCUIT B...

Страница 58: ...POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION Figure 50 CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TE...

Страница 59: ...s Mixing Valve Metal Drain Pan 6 15 2cm Air Gap Max Adequate Drain set to 120 F 48 8 C or lower Mixing Valve Figure 52 TYPICAL ONE TEMPERATURE SYSTEM PIPING INSTALLATION All Models Figure 53 SAMPLE MI...

Страница 60: ...ixing Valve Manual Shut Off Valve Typ Mixing Valve 180 F Max Figure 54 AIR HANDLER PIPING INSTALLATION All Models Figure 55 POLARIS WITH AUXILLARY STORAGE TANK One or Two Temperature System With or Wi...

Страница 61: ...61 NOTES...

Страница 62: ...62 NOTES...

Страница 63: ...For Tech Support please call PGC models 1 800 456 9805 SPC models 1 800 365 0024 BSS BTS models 1 800 527 1953 Copyright 2016 A O Smith Corporation All rights reserved...

Отзывы: