Polaris BSS Скачать руководство пользователя страница 25

25

Hose Clamp

3" Plastic Pipe

Adaptor Rubber Boot

Outer Clamshell Housing

 3" x 3" x 2"

DWV Fitting

Piped To

External Air

Supply

Figure 15. Air Inlet Piping

Adaptor

Rubber Boot

Remove

Filter Media

Filter Media shown inside

the Outer Clamshell Housing

Outer Clamshell

Housing

NOTE: if found difficult to

reattach the outer clamshell

housing to the internal clamshell

housing - apply a thin layer of silicone

grease to the surface of the black rubber

support of the Filter Media. 

                        

Figure 16. Filter Media

DIRECT VENT AIR INTAKE MOISTURE PROTECTION

The air intake piping in a direct vent system will normally not 

have any moisture accumulation in it. However, in certain cases, 

moisture may build up and needs to be drained. Typical situations 

include, but are not limited to:

• 

Cold outdoor temperature, particularly if the air inlet is short,

• 

Heater being used mostly for space heating,

• 

Air inlet pipe has vertical rise near the heater and,

• 

High outdoor humidity.

Installations with any of these conditions are required to provide 

a  moisture  drain  with  a  trap  that  flows  to  a  waste  drain.  See 

Figure  17.  Install  a  drain  tee  assembly  and  a  trap  in  the  inlet 

vent as close to the water heater as possible. This is to drain any 

water that may be in the combustion air pipe and prevent it from 

entering the blower. The drain tubing in any installation should 

have a loop trap and flow to an appropriate waste drain. The air 

intake drain line must be entirely separate from the exhaust vent 

outlet condensate line.

INSTALL TEE FITTING AS CLOSE TO 

WATER HEATER INTAKE AIR

CONNECTION AS POSSIBLE

INTAKE AIR CONDENSATE TEE INSTALLATION

FIELD SUPPLIED 

3"x 3"x 1/2" TEE 

WITH HOSE BARB 

FITTING INSTALLED

FACTORY

INTAKE AIR

CONNECTION

INTAKE

AIR

PIPING

CONNECT FIELD 

SUPPLIED FLEXIBLE 

DRAIN HOSE TO BARB

FITTING AND FORM A 

LOOP WATER TRAP IN 

DRAIN HOSE

RUN DRAIN HOSE 

TO SUITABLE FLOOR 

DRAIN SEPARATELY FROM 

OTHER CONDENSATE DRAINS

Figure 17

HORIZONTAL VENT TERMINAL INSTALLATION

NOTE: 

If you are installing your system so that it vents through the 

roof, please refer to Vertical Vent Terminal Installation on Page 26.

1. A f t e r   t h e   p o i n t s   o f   t e r m i n a t i o n   h a v e   b e e n 

determined  (see  Vent  Pipe  Termination  on  page  23)

 

use  the  cover  plates  as  templates  to  mark  the  holes  for

 

the vent pipes to be inserted through the wall. BEWARE OF 

CONCEALED WIRING AND PIPING INSIDE OF WALL. If the 

vent terminals are being installed on the outside of a finished 

wall, it may be easier to mark both the inside and outside wall. 

Align  the  holes  by  drilling  a  hole  through  the  center  of  the 

template from the inside through to the outside. The template 

can  now  be  positioned  on  the  outside  wall  using  the  drilled 

holes as a centering point for the template.

  

A.) MASONRY SIDE WALLS Chisel an opening approximately 

  

1/2” (1.3 cm) larger than the marked circle.

    B.) WOODEN SIDE WALLS Drill a pilot hole approximately 

     

one  quarter  inch  outside  of  the  marked  circle.  This

 

     

pilot  hole  is  used  as  a  starting  point  for  a  saws-all  or

 

     

sabre saw blade. Cut around the marked circle staying

 

     

approximately  one  quarter  inch  outside  of  the  line.

 

     

(This  will  allow  the  vent  pipe  to  easily  slide  through

 

     

the  opening.  The  resulting  gap  will  be  covered  by  the

 

     

vent  terminal  cover  plates.)  Repeat  this  step  on  the

 

     

inside wall if necessary.

2.  Cut  a  length  of  pipe  about  3.5”  (8.9  cm)  longer  than  the

 

  wall thickness at the opening.

3.  Glue the air intake terminal to the section of the pipe.

4.  Slide the wall plate over pipe to stop against air intake terminal.

5.  Place a bead of caulking (not supplied) around the gap between

 

  the  pipe  and  the  wall.  Place  some  of  the  caulking  on  the

 

  back of the plate to hold it against the wall after installation.

6.  If the air intake pipe is installed up to the wall, with a coupling on the

 

  end against the wall opening, the pipe with the air intake terminal can

 

  be prepared for gluing before inserting through the wall. Slide the

 

  pipe through the wall and insert into coupling on the other side of

 

  the wall. See Figure 18 and Figure 19.

7. 

Refer to Figure 11 in “Vent Pipe Termination” for standard and 

alternate vent termination dimensions.

8. 

Refer to Figure 20 below for the Alternate Horizontal Termination 

installation.

Figure 18

Figure 19

Содержание BSS

Страница 1: ...tly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WH...

Страница 2: ...take Moisture Protection 25 Horizontal Vent Terminal Installation 25 Vertical Vent Terminal Installation 26 Termination Clearances Sidewall Direct Vent 27 Direct Vent Installation Diagrams 28 Concentr...

Страница 3: ...ot follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in injury or death T...

Страница 4: ...Explosion Hazard Overheated water can cause water tank explosion Properly sized Temperature Pressure Relief Valve must be installed in the opening provided Verify the power to the water heater is tur...

Страница 5: ...5 GENERAL SAFETY INFORMATION...

Страница 6: ...nderstand instruction manual Breathing Hazard Carbon Monoxide Gas Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION Fire and Explosion Hazard Le...

Страница 7: ...tally vented gas fueled heating appliance or equipment The sign should read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Страница 8: ...These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed as shown Particular attention should be given to th...

Страница 9: ...8 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 cm 123 19 55 88 40 102 87 104 14 16 19 13 97 16 82 50 130 Inches 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5 8 cm 165 7 55 88 40 138 43 139 7 16 19 13 97 16...

Страница 10: ...pressure must be maintained under both load and no load dynamic and static conditions Table 3 RECOVERY CAPACITIES Input Recovery Capacities Rating Btu hr Rating kW Temp Rise F 30 40 50 60 70 80 90 100...

Страница 11: ...at the bottom of heater behind the Access Doors 1 30 11 15 2 3 23 34 33 CAUTION HARNESS HAS 120 VAC IN OPERATION See Venting Installation and Condensate Piping for more information Figure 2 34 GALLON...

Страница 12: ...ation 50 GALLON UNIT FEATURES AND COMPONENTS CONT Figure 3 50 GALLON UNIT This is a view of the area at the bottom of heater behind the Access Doors 1 2 3 15 32 27 33 29 32 24 26 20 19 12 11 25 13 28...

Страница 13: ...ndensate Drain Outlet 13 Enable Disable Switch 14 Hot Water Outlet 15 Gas Supply 16 Main Manual Gas Shutoff Valve 17 Union 18 Inlet Water Shutoff Valve 19 Cold Water Inlet 20 T P Relief Valve 21 Ratin...

Страница 14: ...pressure switch that requires an increase in negative pressure to change the electrical contacts from normally closed to open The switch is connected to the pressure tap on the PVC pipe connected to...

Страница 15: ...ater heater close to a 120 VAC power supply See Power Supply on Page 18 for requirements 8 Locate the water heater where an adequate supply of fresh air for combustion and ventilation can be obtained...

Страница 16: ...ter heater Do not cover the outer door thermostat or temperature pressure relief valve Do not cover the instruction manual Keep it on the side of the water heater or nearby for future reference Doobta...

Страница 17: ...d at or above the input Btu hr rating of the water heater they supply 2 Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heate...

Страница 18: ...4 Water Temperature F C Time for 1st Degree Burn Less Severe Burns Time for Permanent Burns 2nd 3rd Degree Most Severe Burns 110 43 3 normal shower temp 116 46 7 pain threshold 116 46 7 35 minutes 45...

Страница 19: ...ed in the cold water supply line an expansion tank must be installed between the check valve and the water heater s cold water inlet Set storage tank temperature five degrees lower than the water heat...

Страница 20: ...ature Pressure Relief Valve on the water heater each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized rated and approved Temperatu...

Страница 21: ...the building In cold climates it is recommended that the discharge pipe be terminated at an adequate drain inside the building Shall not have any valve or other obstruction between the temperature pr...

Страница 22: ...bustion air intake and the exhaust vent terminal Refer to Horizontal Vent Terminal Installation on Page 25 and Vertical Vent Terminal Installation on Page 26 GENERAL VENTING INSTRUCTIONS The following...

Страница 23: ...e personal injury death or substantial property damage Installations must comply with applicable national state and local codes For Canadian installation Polypropylene vent must be listed as a ULC S63...

Страница 24: ...000 ft 610 m to 7 700 ft 2 347 m IMPORTANT Do not use vent elbows in this vent pipe installation See Figure 12 90 Short Sweep Elbow 90 Long Sweep Elbow 45 Sweep Elbow Correct Fittings Incorrect Fittin...

Страница 25: ...hat it vents through the roof please refer to Vertical Vent Terminal Installation on Page 26 1 A f t e r t h e p o i n t s o f t e r m i n a t i o n h a v e b e e n determined see Vent Pipe Terminatio...

Страница 26: ...nings above anticipated snow levels FLAT ROOF INSTALLATION On flat roof installations the air intake and the exhaust vent terminations must be a minimum of 24 inches 60 cm above any parapet vertical w...

Страница 27: ...ir supply inlet into building or combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm f...

Страница 28: ...uations See the section on Direct Vent Air Intake Moisture Protection on page 25 Figure 24 SIDEWALL VENT INSTALLATION ALL MODELS See Note 3 See Note 3 Drain Pan Piped To Adequate Drain See Note 1 See...

Страница 29: ...t of a qualified installer or qualified service technician see Page 8 All precautions in the literature on tags and labels attached to the unit must be observed Follow all safety codes Wear safety gla...

Страница 30: ...ARIS UNITS 175 000 199 000 BTU HR MODELS When using two water heaters with inputs of 175 000 BTH HR or above install vent terminations using either Method A or Method B below Figure 33 When using thre...

Страница 31: ...pany will have to install a properly sized gas meter Make sure the gas supplied is the same type listed on the water heaters rating label The gas piping must be installed according to all local and st...

Страница 32: ...y of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases at 11 inches water column pressure Based on a Pressure Drop of 0 5 Inch Water Column Additional tables are available in th...

Страница 33: ...ay coil to this circuit This will damage the CCB circuit board and is not covered under the limited warranty CONNECTING AN EXTERNAL SUPERVISORY CONTROL The enable disable circuit is accessed from the...

Страница 34: ...or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot wat...

Страница 35: ...120 F Status Heating MENU HELP GAS OFF O N Figure 38 HIGH TEMPERATURE LIMIT CONTROL ECO This water heater is equipped with an ECO energy cut out non adjustable high temperature limit switch The ECO i...

Страница 36: ...ion of the various operational states The Desktop screen also displays animated Status Icons to convey operational information see Table 12 on Page 37 for descriptions of the Status Icons OVERVIEW The...

Страница 37: ...control system or when the Enable Disable switch located at the base of the water heater is in disable position The Combustion Blower is being energized The Spark Igniter is being energized See Spark...

Страница 38: ...ot reset the control system if the condition that caused the Fault has not been corrected Heating Disabled The heating is disabled by the Enable Disable switch located at the base of the water heater...

Страница 39: ...will be displayed Tank Temperature 71 F Operating Setpoint 120 F Status Standby HELP MANUFACTURER MODEL INFORMATION MENU The Main Menu is where all control system menus are listed see Table 14 on page...

Страница 40: ...fferential Adjustment on page 39 Temperatures HELP BACK Operating Setpoint 120 F Differential 8 F Tank Temperature 120 F Tank Probe Offset 0 F HEATER STATUS MENU DESCRIPTION ACTION DISPLAY Press Heate...

Страница 41: ...ersion Software version for user interface module Use External Enable Enables Disables the external enable circuit External Enable Status Displays whether or not the external enable circuit has been a...

Страница 42: ...last nine 9 Fault andAlert messages with a time stamp The newest event will replace the oldest Press the Fault to view details for each Fault or Alert message stored Fault History HELP BACK 1 Upper T...

Страница 43: ...to Yes and press ACCEPT to save the new setting NOTE The Access Code at the bottom of the Service Contact Information screen is for manufacturing engineering purposes only There are no user settings...

Страница 44: ...Sequence of Operation See the Sequence of Operation Flow Chart on page 49 Ensure the water heater is properly grounded Flame sensing requires an adequate earth ground If the water heater is not proper...

Страница 45: ...42 On the water heaters covered by this manual there are test ports for supply and manifold gas pressure readings on the gas control valve Using a small flat tip pocket screw driver open the needle v...

Страница 46: ...t a t s o m r e h t e h t t e S o t s e t u n i m 5 e v i f t i a W s a g y n a t u o r a e l c s a g l l e m s n e h t u o y f I n i B w o l l o F P O T S u o y f I l e b a l s i h t n o e v o b a n...

Страница 47: ...The display CCB and other electrical components will still be energized and the display will read Water Heating Disabled 3 Close Main Gas Shutoff Valve see Figure 37 on page 31 GAS INPUT RATE The gas...

Страница 48: ...represents some of the most critical installation requirements that when overlooked often result in operational problems down time and needless parts replacement This is not a complete list Before pe...

Страница 49: ...setting a heating cycle is activated Igniter is energized 24 V Gas Control Valve is energized gas flows to Main Burner 24 V Gas Control Valve de energized 24 V Gas Control Valve de energized Is flame...

Страница 50: ...e to have the complete water heater Model Number Serial Number and Series Number available This information can be found on the rating plate affixed to the water heater For more information or technic...

Страница 51: ...l continue to lock out DIAGNOSTIC CHECKS Turn off power to the water heater before performing any service Electrical Shock Hazard Label all wires prior to disconnecting when performing service Wiring...

Страница 52: ...continuity when the blower is off and closed shorted when the blower is on Replace the switch if necessary ADVANCED BACK 0 days 0 hrs 0 mins ago Error Code A7 1201 Blocked Air Intake Restriction in ai...

Страница 53: ...the valve being slightly opened Not shown in Figure 46 F The drain valve may be leaking at the tank fitting Not shown in Figure 46 G Leakage from recirculation plug or pipe connection Not shown in Fig...

Страница 54: ...n the hose clamp at the adaptor rubber boot and slide the plastic pipe out and away from the adaptor rubber boot See Figure 14 in Integrated Filter Installation Remove the adaptor rubber boot containi...

Страница 55: ...ter heater drain valve and terminate it to an adequate drain 7 Open the water heater drain valve and allow all the water to drain from the storage tank 8 Close the water heater drain valve when all wa...

Страница 56: ...CONTROL BOARD LAYOUT 11 12 1 J16 J5 J3 J13 J4 J17 J10 J9 J14 J15 J1 J6 J12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 6 6 6 7 7 8 8...

Страница 57: ...iolet CCB J3 5V Data Data D gnd SDA data SCL data Write protect 5V Dgnd CCB J12 2 Red 3 Green 4 White Brown 5 White Blue 6 White Orange Key Gas Valve L1 Neutral Protective Earth MAIN INPUT 3 CIRCUIT B...

Страница 58: ...POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION Figure 50 CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TE...

Страница 59: ...s Mixing Valve Metal Drain Pan 6 15 2cm Air Gap Max Adequate Drain set to 120 F 48 8 C or lower Mixing Valve Figure 52 TYPICAL ONE TEMPERATURE SYSTEM PIPING INSTALLATION All Models Figure 53 SAMPLE MI...

Страница 60: ...ixing Valve Manual Shut Off Valve Typ Mixing Valve 180 F Max Figure 54 AIR HANDLER PIPING INSTALLATION All Models Figure 55 POLARIS WITH AUXILLARY STORAGE TANK One or Two Temperature System With or Wi...

Страница 61: ...61 NOTES...

Страница 62: ...62 NOTES...

Страница 63: ...For Tech Support please call PGC models 1 800 456 9805 SPC models 1 800 365 0024 BSS BTS models 1 800 527 1953 Copyright 2016 A O Smith Corporation All rights reserved...

Отзывы: