42
Min. mixer temperature
Using this parameter it is possible to restrict Chance of
setting to low preset mixer circuit temperature. Automatic
control (i.e. periodical temperaturę reduction) also will not
cause reduction in preset temperature below value set in this
parameter.
Max. mixer temperature
Parameter serves two functions:
- allows restricting setting too high mixer preset
temperaturę. Automatic control also will not cause exceeding
preset temperature above value set in this parameter.
- with parameter mixer setting = activated FLOOR is also
limit temperature of mixer sensor when mixer pump is
deactivated. For floor heating set the value below 45 degrees
C – 50 degrees C or other if producer of materials used for
floor or CH installation designer state differently.
Valve full opening time
Set full valve opening time given at the plate of valve
servomotor, i.e. 140s.
Off by thermostat
Setting the parameter on YES value causes closing of mixer
servomotor and deactivating mixer pump after disconnecting
joints of room thermostat. This is not recommended because
the heated room can be too cool.
Mixer input dead zone *
Setting parameter determining value of temperaturę dead
zone for mixer controlling circuit. The controller regulates
mixer in such a way to keep the temperature of mixer cycle
equal to preset value. However, avoid too frequent
movements of servomotor, which can shorten its long-life
usage. Regulation is undertaken only when measured
temperature of mixer cycle will be higher or lower than
preset value by the value bigger than mixer dead zone.
14.6
ADVANCED PARAMETERS
Show advanced setup
Options available:
YES (displays hidden parameters which edition is not
recommended)
NO (hides hidden parameters)
15
DEFAULT SETTINGS RESTORING
Default settings restoring
Restoring service settings settings from main menu are
restored.