weather sensor. Use following parameters to 
activate this function: 

Menu 

→ 

Summer/Winter 

→ 

SUMMER 

Mode

 → 

Auto 

If  the  automatic  detection  of  summer  mode 
is  switched  on,  you  can  set  the  parameters: 
Start temperature summer mode, so outdoor 
temp. above which the summer mode will be 
switched  on  and  and  outdoor  temp.  below 
which  the  SUMMER  mode  will  be  switched 
off. The parameters are grouped in

 Menu 

→ 

Summer / Winter. 

8.15

 

HOT WATER FEEDER 

DISINFECTION 

 

The controller can automatically, periodically 
make HW silo warm up to 70 degrees C. It is 
done to remove bacterial flora.  
 

 

It  is  absolutely  important  to  inform 
all the inmates about activating the 
disinfection  function.  There  is  a 
danger  of  scalding  with  HW  hot 
water. 

Once  a  week  at  night  between  Sunday  and 
Monday  at  2  a.m.  the  controller  increases 
temperature  of  HW  silo.  After  10  minutes  of 
keeping  the  silo  at  70  degrees  C  the  HW 
pump  is  deactivated  and  the  silo  returns  to 
its  normal  operation.  It  is  not  advisable  to 
activate  disinfection  function  while  the 
service of HW is deactivated. 
 

8.16

 

MIXER CIRCLE SETTINGS 

Settings of first mixer circle are in the menu: 

Menu 

 Mixer 1 settings  

Settings  for  other  mixers  are  in  following 
sections  of  the  menu  and  are  identical  in 
each cycle. 
 

 

Mixer  settings  without 

weather 

sensor 

It  is  required  to  set  manually  desired 
temperature  in  mixer’s  heating  cycle  using 
parameter 

Preset  mixer  temperature,

e.g.  50 

degrees C. Such should be a value to provide 
required room temperature. 
 
After connecting a room thermostat, value of 
decline  in  preset  mixer  temperature  from 

thermostat should be set. (parameters 

mixer 

room thermostat

 e.g. 5 degrees C. This value 

should  be  chosen  experimentally.  A  room 
thermostat  can  be  a  traditional  one  or  a 
room panel ecoSTER200. After activating the 
thermostat, mixer preset temperature will be 
reduced.  When  this  value  is  reduced 
correctly  then  room  temperature  increase 
will be stopped.  
 

 

Mixer with weather sensor setting 

Set  parameter 

mixer  weather  control 

in 

position  on.  Adjust  weather  curve  according 
to point 8.17 

 

Using parameter 

paralel curve movement 

set 

required  room  temperature  according  to 
formula: 
Required  room  temperature  =  20°C  + 
heating curve paralel movement.  
Example: 
To  reach  room  temperature  25°C  value  of 
heating  curve  movement  must  be  set  for 
5°C. To reach room temperature 18°C value 
of  heating  curve  paralel  movement  must  be 
set for -2°C. 
 
In  this  configuration  a  thermostat  can  be 
connected. It will level inaccuracy of heating 
curve adjustement in case when its value will 
be too big. In such case value of decrease of 
preset  mixer  room  temperature  from 
thermostat  should  be  set  i.e.  for  2°C

.

After 

discontecting  thermostat  plugs  preset  mixer 
cycle temperature will be reduced. By correct 
adjustement  of  this  reduction  will  stop 
temperature  increase  of  temperature  in 
heated room. 
  

 

Mixer with weather sensor and room 
panel settings  

Set  parameter 

Mixer  weather  control

.  In 

position off. 

 

Adjust weather curve according to point 8.17 
 
Controller  ecoSTER200  automatically  moves 
the heating curve depending on preset room 
temperature. 

The 

controller 

relates 

adjustements to 20 degrees C, i.e. for preset 
room  temperature  =  22  degrees  C  the 

Содержание Cieplo ecoMAX850P2-C

Страница 1: ...ER TOUCH non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 0 APPLIES FOR HARDWARE MODUL A PANEL v02 XX XX v 02 XX XX Burner Controller ecoMAX850P2 C FOR BOILERS FUELLED WITH PELLETS 09 2015 Modul B Modul C ...

Страница 2: ......

Страница 3: ...NVIRONMENTAL CONDITIONS 26 12 2 WYMAGANIA MONTAŻOWE 26 12 3 INSTALLATION 27 12 4 ELECTRIC CIRCUIT CONNECTION 27 12 5 SAFETY CONNECTIONS 28 12 6 ELECTRIC SCHEME 29 12 7 TEMPERATURE SENSORS CONNECTION 30 12 8 WEATHER SENSORS CONNECTION 30 12 9 WEATHER SENSORS CHECKING 30 12 10 OPTICAL SENSOR CONNECTION 31 12 11 MIXERS ROOM TEMPERATURE CONNECTION 31 12 12 BOILER ROOM THERMOSTAT CONNECTION 31 12 13 RE...

Страница 4: ...eeder etc The controller is for boiler producers The boiler producer before its use should check if the cooperation between the controller and the boiler is correct and is not dangerous The controller is not a spark safe device It means that in emergency mode may be the source of a spark or high temperature which together with dust or flammable gases can cause fire or explosion The controller must...

Страница 5: ...ser s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get aquainted with both parts of the user s manual We do not take responsibility for damages caused by failing to observe the following user manual 4 DOCUMENTATION STORAGE We advise you to keep carefully this u...

Страница 6: ......

Страница 7: ...USER MANUAL OF THE CONTROLLER ecoMAX850P2 C ...

Страница 8: ...y HUW settings Preset HUW temperature HUW pump mode Off Priority No priority HUW cont hysteresis HUW disinfection Sommer Winter SUMMER mode Summer Winter Auto Activ temperature SUMMER Deactv temperature SUMMER Mixer settings 1 2 3 4 5 5 Preset mixer temperature Mixer room thermostat Weather control mixer Heating curve Mixer Curve shift Room temperaturę factor Night time decrease Boiler Mixer 1 5 H...

Страница 9: ...g blowing operation 6 Symbol signalling fuel feeder operation 7 Symbol signalling central heating CH pump operation 8 Symbol signalling central heating pump operation HW 9 Measured temperature of hot water boiler HW 10 Preset hot water HW boiler temperature 11 Clock and weekday 12 Part of the screen coshared between two icons match symbolizes operating heater and the digit next to it stands for a ...

Страница 10: ...ange of respective service parameters of the controller Menu Boiler settings Preset boiler temperature Menu Mixer settings 1 5 Preset mixer temperature The parameter value Preset boiler temperature is by controller bypassed when the preset boiler temperature is controlled by wheather sensor Regardless of that the preset boiler temp is automatically increased to load the hot user water tank and pow...

Страница 11: ...f to SUPERVISION mode Controller is equipped with boiler s power modulation mechanism which allows for gradual power reduction when approaching the preset temperature There are three power levels MAX MED MIN power Current power level is displayed on the screen as 3 segmented indicato rat the left side of boiler s icon Each level can be allocated with seperate fuel feeding times and Air flush inten...

Страница 12: ... not cause further increase in temperature Burner s power in SUPERVISION mode and other parameters of Supervision are grouped in menu Menu Service settings Boiler settings Supervision Parameters of SUPERVISION mode are to be set in accordance to burner boiler producer s recommendations They should be so chosen to prevent the furnace from burning off during boiler s pauses the furnace should not at...

Страница 13: ...r a period of 10 minutes there has been no growth 8 11 HOT WATER SETTINGS The controller regulates temperature of the silo of Hot Water HW providing that the temperature sensor is connected When the sensor is disconnected the information about it is displayed in the main window By selecting Menu HUW settings HUW Pump mode the user is able to deactivate feeding the silo parameter Deactivated settin...

Страница 14: ...ing a room thermostat value of decline in preset mixer temperature from thermostat should be set parameters mixer room thermostat e g 5 degrees C This value should be chosen experimentally A room thermostat can be a traditional one or a room panel ecoSTER200 After activating the thermostat mixer preset temperature will be reduced When this value is reduced correctly then room temperature increase ...

Страница 15: ...g too high value of room temperature factor may cause cyclic room temperature fluctuations 8 17 WEATHER CONTROL Depending on measured outside temperature automatically controlled can be either preset boiler temperature and mixer cycles temperatures By correct adjustment of heating curve temperature of heating circuits is counted automatically depending on value of external temperature Thanks to th...

Страница 16: ...e beginning and end of a given period of time Time periods Above are examples of night time decrease the preset boiler temperature lasting from 22 00 till 06 00 and the reduction from 09 00 to 15 00 Attention defining time periods during one day must be started at 00 00 Time period is omitted by setting period reduction for value 0 even if scope of hours is set in it 8 19 CIRCULAR PUMP CONTROL Att...

Страница 17: ...fuel level indicator The indicator will pulsate until programming point referring to minimum fuel level Decreasing level of fuel in the silo should be monitored constantly When fuel level reaches expected minimum parameter value should be set this way Menu Boiler settings Fuel level Fuel level calibration Fuel level 0 8 21 COOPERATION WITH ADDITIONAL FEEDER After connecting additional B module the...

Страница 18: ...wer engine It enables to check if the device is operating correctly and if it is connected properly Entering manual control is possible only in STAND BY mode when silo is switched off OFF the device is turned off ON the device is turned on Attention long lasting activating of fan feeder or other device may cause danger ...

Страница 19: ......

Страница 20: ......

Страница 21: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX850P2 C ...

Страница 22: ......

Страница 23: ...referring to gravity installations If return sensor is installed closely it is necessary to isolate it thermically from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same time heating water returning to the silo RECOMMENDED SETTINGS Parameter Setting MENU Preset boiler temperature 75 80 C menu boil...

Страница 24: ...ttings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HUW settings Activating operation buffer service activated menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer servi...

Страница 25: ...menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer service 1 2 3 4 active CH menu service settings mixer 1 4 settings Max Mixer preset temperature 1 2 3 4 70 menu service settings mixer 1 4 settings Mixer heating curve 1 2 3 4 0 8 1 4 menu mixer 1 4 settings M...

Страница 26: ... sunrays Temperature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 12 CONTROLLER INSTALLATION 12 1 ENVIRONMENTAL CONDITIONS Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller can not be used in conditions...

Страница 27: ...ontroller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50Hz Features of installation 3 way with protecting wire made according with valid law After deactivating the controller with the keypad there still can be a dangerous voltage on the connections Before...

Страница 28: ...Wires inside the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling wire Length of isolation of external tire of wires should be minimal maximum 60mm If it is necessary to longer isolate the wire tire they should be connected with each other or other wires close to the connector In this case when a wire gets loose fro...

Страница 29: ...ection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additional modules B module B allows to service additional two mixer cycles and heating buffer cycle MX 03 additional module allows to service two additional mixers and circular pump A Lambda sond module L N PE electrical power 230V FU fuse STB connection to ...

Страница 30: ... 12 8 WEATHER SENSORS CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be installed on the coolest wall of the building Usually it is the northern wall under the roof The sensor shoul not be exposed to direct sunrays and rain The sensor should be installed at least 2 m above the ground far away from windows chimneys and other sources of heat which could ...

Страница 31: ...universal or ecoSTER T1 if room panel ecoSTER200 is connected Menu Service settings Boiler settings Thermostat selection For thermostat switch on the CH boiler pump without switching off the boiler set the parameter Thermostat pump deactivating on YES Menu Service settings Boiler settings Pump off by thermostat 12 13 RESERVE BOILER CONNECTION The controller can control work of additional gas or oi...

Страница 32: ...ivation of additional boiler When pellet boiler is fired up and its temperature exceedes preset value i e 25 degrees C then controller switches off additional boiler it will give constant power AC 6V for terminals 39 40 It will power the coil of transmitter and disconnecting its joints After decreasing boiler temperature below parameter temperature of additional boiler switching off the controller...

Страница 33: ...st first disable the reserve boiler control To do this you should in the menu Service settings Boiler settings Reserve boiler Set zero value of its deactivating temperature External alarm device connection where 1 controller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing...

Страница 34: ...ve opening time should be written on data plate of servomotor i e 120s Connect electrical power of the controller and activate it so the mixer pump is working Choose the direction in which servomotor opens and closes To do so switch the button to manual control and find position in which temperature in mixer circuit is maximal in controller it is position 100 ON and value position when temperature...

Страница 35: ... of fuel feeder Safety temperaturę limiter must have nominal voltage at least 230V and should have valid admission documents In case of not installing the limiter terminals 1 2 are to be connected by a bridge The bridge must be made with insulated wire with diameter at least 0 75mm2 With insulation which is thick enough to meet safety standards of the boiler 12 18 ROOM PANEL CONNECTION It is possi...

Страница 36: ...e time Fan output Grate Blowing power supervision Blowing pause supervision Min airflow output Fuel shortage detection time Maximum feeder temperature Operation time of additional feeder Boiler settings Thermostat select Return protection Minimum boiler temperature Maximum boiler temperature Reserve boiler Alarms Boiler cooling temperature Parameter A B C FL Off by thermostat CH and HUW settings C...

Страница 37: ...e Switches the burner into THERMOSTAT mode i e for working in bakery The burner operates with maximum power without modulation of power The burner deactivates with disconnecting thermostat joints 28 29 Boiler temperature sensor does not influence feeder operation Cycle time OPERATION Time of whole fuel feeding cycle in OPERATION mode OPERATION mode time feeding time OPERATION feeder pause time Fue...

Страница 38: ...peration in Supervision mode Adjust value in such a way to burn feeding fuel in Supervision mode with low fumes emission Grate Blowing power supervision The duration of the fan blow in the supervision in grate mode Blowing pause supervision Interval between blows in the supervision in grate mode Min airflow output Minimum fan power in which can be chosen by the user It is only used to limit the ac...

Страница 39: ...cle Instead this it is recommended to use bigger preset temperatures of boiler 70 75 what in combination with installation with 4 way valve with servomotor it will cause automatic increase return temperature Minimum boiler temperature Minimum preset boiler temperaturę which can be set in user menu and minimum temp which can be set automatically by controller i e from night reductions etc Maximum b...

Страница 40: ...ging the controller Due to breakdown of the controller water in the silo can heat up to dangerous temperature It is necessary to use additional protection in the form of thermostatic valves Boiler inc by HUW Mixer Parameter determines how high the boiler temperature will be increased to load HW silo buffer and mixer cycle Temperature increase is only realizing when it is necessary When preset boil...

Страница 41: ...wers floor installation Maximum power of mixer cycle is limited to value of parameter max preset mixer temperature Attention After choosing option FLOOR it is necessary to set parameter max mixer preset temperature on such a value to not damage the floor and avoid scalding risk Pump only When mixer cycle temperaturę exceeds value set in parameter mixer preset temperaturę feeding of mixer pump is s...

Страница 42: ...ime given at the plate of valve servomotor i e 140s Off by thermostat Setting the parameter on YES value causes closing of mixer servomotor and deactivating mixer pump after disconnecting joints of room thermostat This is not recommended because the heated room can be too cool Mixer input dead zone Setting parameter determining value of temperaturę dead zone for mixer controlling circuit The contr...

Страница 43: ...2 FEEDER MAX TEMP EXCEEDING Alarm appears after exceeding feeder temperaturę above service parameter MENU Service settings Burner settings Max burner temp If the feeder temperature increases above this value the controller will begin burning off procedure Alarm is deleted automatically after feeder temperature decrease by 10 C Function which protects against back fire does not work when feeder sen...

Страница 44: ...he silo 16 7 UNSUCCESSFULL ATTEMPT TO LOAD THE TANK This is so called silent alarm reminder It will take place by failed attempt of feeding fuel from additional silo In case when through configured time of feeding the silo installed sensor not detects increase of fuel the reminder is displayed This signalization does not cause activating automatic boiler operation there is only a warning displayed...

Страница 45: ... If this parameter is set on OFF then Lambda Sond readings will not have influence on controller s operation Amounts of air for given burner power are set in MENU Boiler settings Output modulation Description of remaining parameters relaed to Lambda sond Prameter Blow in output scope sets permissible scope of variability of airflow power by work using lambda sond Parameters Dynamics and Reaction t...

Страница 46: ...and twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional ffeder is not working module B Check if feeder wires are correctly connected to terminals Check if there is a jumper on terminals 1 2 of module B Check if feeder engine is not damaged In case when engine work can be heard and fuel is not provided check the feeder with its us...

Страница 47: ...de after closing the valve return temperature must increase above value of parameter Minimum return temperature The cause may be calibration of mixer valve wait until calibration is finished Active calibration is marked CAL in menu INFORMATION 20 COTROLLER CONFIGURATION BY BOILER PRODUCER The producer of boiler burner should adjust program parameters in controller to given type and power of the bu...

Страница 48: ......

Страница 49: ...ul Wspólna 19 Ignatki 16 001 Kleosin Poland tel 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www pum pl www plumelectronics eu ...

Отзывы: