NOTICE:
These are guidelines for successful venting
of your pellet appliance. The more vertical rise you can
obtain in your system, the better it will perform. Horizontal
vent runs can accumulate ash and will need to be cleaned
more often. Try to keep them as short as possible.
We strongly recommend a minimum of 60 inches (1.5m)
vertical, however above the eave is preferred.
Both installations are approved for mobile home installations.
Must use 3 or 4 inch (76 to 102mm) “L” or “PL” Listed pellet
venting or Listed double wall pipe and authorized Outside
Air Kit in mobile homes. Single wall pipe is approved for
residential installations only.
Air Clearance to Pipe:
This appliance was tested with standard 3 inch (76mm)
Listed pellet vent.
Pellet pipe manufacturers Listed reduced clearance pipe
may be use for reduce clearance from 3 inch (76mm) air
clearance to no less than 1 inch (25mm) air clearance to
combustibles for approved Listed pellet pipe.
Follow pipe manufactures listed air clearances to
combustibles and installation instructions for all
reduced air clearances installations.
C. Vertical into Existing Class A Chimney
B. Through The Wall & Vertical - External -
Horizontal
A. Vertical - Interior - Typical Installation
9
9
Vent Systems
PREFERRED METHOD #1
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
follow pipe manufacture
listed clearance
12 in.
(305mm)
Minimum
Clean-out T
PREFERRED METHOD #2
Non-combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support
Bracket
Every 60 in.
(1.5 m)
12 in.
(305mm)
Minimum
Rain Cap
Flashing
2 in. (5.08 mm) Minimum
6 in. (152 mm)
Minimum
Firestop
Flashing
Rain Cap
Non-combustible Hearth Pad
Follow vent manufacturer’s
clearances for reduced clearances
12 in. (305mm) Minimum
Ceiling Support
6 in. (152mm) Flue
Connector
6 in. (152mm) Class A
Chimney Connector
Adapter
6 in.
(152mm)
Min.
follow pipe manufacture
listed clearance
Clean-out T