209 Mains quality limit
exceeded
If mains voltage on feeding point is permanently too high:
Check voltage dip on mains lead.
Inform power plant operator.
Check value for mains quality limit.
210
211
Mains frequency above or
below limits
If inverter is running on emergency power (different main
frequency):
No measure required.
212
to
213
Diagnosis support during
service
Provide the service with the error code if required.
214
to
218
too high fault current when
switching on
If error occurs frequently:
Check insulation resistance on DC side.
220
to
225
measured temperatures too
high
Check ventilation openings.
226 max. mains current exceeded
Check AC side for short circuit.
230
to
233
Temperature sensor defective
Separate inverter from mains.
Restart inverter.
If measure is not successful:
Call Service.
234
to
261
Diagnosis support during ser-
vice
Separate inverter from mains.
Restart inverter.
If measure is not successful:
Call Service.
262 power supply on interface card
overloaded
Disconnect connections on interface card
Check connections on interface card for short circuit.
If measure is not successful:
Call Service.
Provide the service with the error code if required.
263
to
289
Diagnosis support during
service
Provide the service with the error code if required.
271
to
273
max. AC exceeded
Check AC side for short circuit.