PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Mounting
18
Installation and operating manual: PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Version 05/2010
Mat. No. 737 576-AB
5.5 Connection of the inverter
Note
Terms relating to the alternating voltage side will be combined with
AC
below. Terms relating to the direct voltage side will be combined
with
DC
below.
Danger
Danger to life due to high AC voltage!
Â
Switch off the mains power supply (AC side) before
connecting the inverter (fuse).
Â
Connect inverter exclusively to TN or TT mains
(see IEC 60364-1) with 230 V.
Â
Maximum allowed fuse on alternating voltage side:
40 A, C-characteristics.
Danger
Danger to life due to high DC voltage!
Â
Prior to connecting the inverter, verify that voltage is
applied to the generator-side DC terminal.
Â
Prior to connecting the inverter, verify that the DC
voltage polarity is correct.
Â
Wear insulating protective clothing and face
protection if there is voltage present at the DC input.
Â
Remove DC cable exclusively if inverter is out of
operation.
Caution
Risk of burns due to hot surfaces!
After a longer operation with high power, housing
temperatures of > 60 °C are possible.
Â
Do not touch hot surfaces.
Caution
Material damage due to DC plug connectors that don’t
fit!
Â
Use exclusively DC cable connectors and DC
receptacles of the same type and manufacturer.
Â
Make sure that cable connector in latched in socket
correctly.